COMMERCIAL INSPECTION -2710 CROSSROADS BLVD -2-17-23 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price J
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
5204 04/26/2023 04/05/2023 2023-00011177 $200.00
Less Prepayment $0.00
Total Due— $200.00
City of Waterloo
o, q
(/�/��a
V �p1ER(�O
WATERLOO FIRE RESCUE ;
INSPECTION REPORT 1 \ ii
TIRES PLUS,2710 CROSSROADS BLVD,BLDG 2710 CROSSROADS BLVD,WATERLOO/A S0702
DETAILS
Inspection Date:02/17/2023 j Inspection Type:Annual Inspection(1Yr) 1 Inspection Number:9434 I Shift: N/A i Station: N/A I
Unit: N/A Lead Inspector:JEREMIAH VANDYKE ; Other Inspectors: N/A I Fee:$200.00
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Fire alarm in trouble, needs to be
addressed by licensed fire alarm contractor.
1
0
—74
- ig 1
{
FAIL 509.1 -Identification Fire protection equipment shall be identified in an approved manner.Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements shall be identified for the use of the
fire department.Approved signs required to identify fire protection equipment and
I ;,.- • -,'. _sic; :ee equipment location shall be constructed of durable materials, permanently installed
l and readily visible.
... Inspector:JEREMIAH VANDYKE-Comments:Door located in main garage going into
tire storage area needs signage.Must have"Sprinkler Riser,FACP,&Main Electrical
panel"for description.
\s_ FVt
Vit
Printed on 02/17/2023 @ 14:13
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress lights located in shop and in back
parts area tested and failed.
4
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm need to be inspected by
licensed fire alarm contractor and inspection report uploaded into Compliance
Engine by servicing contractor.
GENERAL NOTES
JEREMIAH VANDYKE-01/06/2023 @ 14:26 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-01/06/2023 @ 14:26 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-01/06/2023 @ 14:26 RE-inspection fee:$200.00
Printed on 02/17/2023 @ 14:13
Page 2 of 3
REINSPECTION DATE
03/19/2023
CONTACT SIGNATURE
Matt Eschweiler Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:02/17/2023 @ 14:13