HomeMy WebLinkAbout250 ANSBOROUGH AVE TOT AL DUL
INVOICE# $80.00
DUE DATE 00411115
INVOICE DATE 2023-
0211512023
0312012023
4'
C
d Remit T°'
kpa�,able an
e MakeChec able
Please f Waterloo Receivable
s9 City Clerk/Accounts R
Customer#: 2�� ATTN: City CI St
715 Mulberryo, IA 50703
WATER
SS PAVILION LE CoNGfZE AV Amount Enclosed
CATTLE
-
25 __--
oo�1A50701 RPAYMENT
WATERLOO,
ATER wITHY°U __--
RETURNTAP PORTION YOUR CORDS (319)291_4323
BILLING INQUIRY:DETACH AND _ P THIS PORTION FOR �R .
E
KE AVE_2.9_23 Total price
iE1012500 ;0
n
INSPECTION 2,000
INSPE ANCY FEE
OCCUPANCY
Cx��
VOICE#
DUE DOE 2023-0001111 meat
DATE 0312012023 Less Prepay
Total Due
CUSTOMER# BILLING0211512023
207 89 City of Waterloo
. < \ ''--.1 (k
,r-a
WA TERL OO FIRE RESCUE ..1.00ERtoo
INSPECTION REPORTIf t
NATIONAL CATTLE CONGRESS PAVILUON,250 ANSBOROUGH AVE,BLD6 250 ANSBOROUGH
AVE,WATERLOO IA 50701
DETAILS
Inspection Date:02/09/2023 ; Inspection Type:Annual Inspection(1Yr) j Inspection Number:7542 1 Shift: N/A I Station: N/A
Unit: N/A ! Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A 1 Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1032.3-Obstructions. A means of egress shall be free from obstructions that would prevent its use,
including the accumulation of snow and ice.
Inspector:JEFF SIEBEL-Comments:NW exit doors blocked with ice/snow.Remove
obstructions.
FAIL 1103.5.1 -Group A-2. Where alcoholic beverages are consumed in a Group A-2 occupancy having an
occupant load of 300 or more,the fire area containing the Group A-2 occupancy shall
be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1.
Inspector:JEFF SIEBEL-Comments:.Per letter sent to National Cattle Congress in
reference to the Pepsi Pavilion by Fire Marshal Weliver a year ago a fire sprinkler
system is required in the pavilion. Please contact Fire Marshal Brock Weliver 319-493-
1136 with plan and expected completion date.See attached code section
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair emergency egress lights:A.SE corner by
women's RR B.NE corner by Men's RR
FAIL 506.1 -Where required. Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire-fighting
purposes,the fire code official is authorized to require a key box to be installed in an
approved location.The key box shall be of an approved type listed in accordance with
UL 1037,and shall contain keys to gain necessary access as required by the fire code
official.
Inspector:JEFF SIEBEL-Comments:Knox box required to be installed with fire
sprinkler system.
Printed on 02/10/2023 @ 13:31
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:provide documentation of dryer vent cleaning to
the outside of the building with signature and date.
GENERAL NOTES
JEFF SIEBEL-02/10/2023 @ 13:14
JEFF SIEBEL-02/10/2023 @ 13:15 annual inspection$80
REINSPECTION DATE
03/09/2023
CONTACT SIGNATURE
Jim Koch L1A-- '� 1
Signed on:02/10/2023 @ 13:15
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:02/10/2023 @ 13:15