COMMERCIAL INSPECTION- 310 W CONGER- 2-8-23 FOR BILLING INQUIRY: (319)291-4323
[Description I Total Price j
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12078 02/15/2023 03/20/2023 2023-00011117 $80.00
Less Prepayment $0.00
Total Due --> $80.00
City of Waterloo
O FIRE RESCUE
WATERLO \ r,-/ ..141
INSPECTION REPORT ,
ELECTRIC PARK BALLROOM,310 W CONGER ST,BLD6 310 W CONGER ST,WATERLOO IA
50701
DETAILS
Inspection Date:02/08/2023 I Inspection Type:Annual Inspection(1Yr) " Inspection Number:7541 I Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL Comments:repair egress lights:A.by lower bar B.egress
lighting hanging by wires
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit/egress lights on west wall of dance
floor above exit doors.
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3.Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if dislodged,do not obstruct
the required means of egress.4.Securing of compressed gas containers,cylinders
and tanks to or within a rack,framework,cabinet or similar assembly designed for
such use. Exception:Compressed gas containers,cylinders and tanks in the process
of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:chain compressed gas cylinder behind upper bar.
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:provide current annual fire alarm inspection
report with all discrepancies corrected.Currently is 3 days overdue.Contractor must
upload online to the compliance engine.
GENERAL NOTES
Printed on 02/10/2023 @ 13:42
Page 1 of 2
JEFF SIEBEL-02/10/2023 @ 08:50 Annual inspection$80
JEFF SIEBEL-02/10/2023 @ 08:51 Hood cleaning due 3/3/23.Fire Sprinkler due 5/17/23 and hood fire suppression due
4/24/23.
REINSPECTION DATE
03/09/2023
CONTACT SIGNATURE
Jim Koch
Signed on:02/10/2023 @ 13:41 CS- (k-1-
INSPECTOR SIGNATURE
JEFF SIEBEL //) V
Signed on:02/10/2023 @ 13:41