HomeMy WebLinkAbout2060 CROSSROADS BLVD .�! INVOICE DATE DUE DATE INVOICE# TOTAL DUE
I PIS 02/15/2023 03/20/2023 2023-00011119 $100.00
%rloo
Customer#: 3989 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CROSSROADS MALL 715 Mulberry St
2060 CROSSROADS BLVD STE 124 WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-2060 CROSSROADS BLVD - 1-27-23 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3989 02/15/2023 03/20/2023 2023-00011119 $100.00
Less Prepayment $0.00
Total Due —* $100.00
City of Waterloo
Li
pTERCO
WATERLOO FIRE RESCUE 9ct,
INSPECTION REPORT ‘;
CROSSROADS MALL,2060 CROSSROADS BLVD,BLDG 2060 CROSSROADS BLVD,WATERLOO/A
4'50702 �+�'
DETAILS
Inspection Date:01/27/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:9269 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE i Other Inspectors:BROCK WELIVER I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Sears building and Sears garage.Fire
alarm system needs to be maintained and deficiency's corrected by licensed
electrician and report up loaded into Compliance Engine by servicing contractor.
Alarm in Trouble mode.Hawkeye alarm has been contacted and figuring contract
information.
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEREMIAH VANDYKE-Comments:5 year inspection is due and dry system
has compressor on backorder for SEARS.
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:DOWNS STAIRS COMPLETE,WORKING ON
UPSTAIRS:Egress lights and Exit signs need to be tested and recorded of the common
space areas and ALL entrances/exits used by mall patrons in the event of an
emergency.CURRENTLY being replaced or repaired.
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:DOWNS STAIRS COMPLETE,WORKING ON
UPSTAIRS:Egress lights and Exit signs need to be tested and recorded of the common
space areas and ALL entrances/exits used by mall patrons in the event of an
emergency.CURRENTLY being replaced or repaired.
Printed on 01/30/2023 @ 08:09
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered,breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEREMIAH VANDYKE-Comments: Missing Ceiling Tiles in tenant and
common spaces: 1.Waterbed store#141.2.Roc fit#113.3.SEARS store both upper
and lower space.4.Pro Nails#215.5.Gordmans.6.Younkers 7.Amish Connection
2602 building.8.Sears Auto garage,ALSO will contact sprinkler company about
turning heads up and pulling down tile/grid system.CURRENTLY being replaced.
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments:Sears building and Sears garage.Fire
alarm system needs to be maintained and deficiency's corrected by licensed
electrician and report up loaded into Compliance Engine by servicing contractor.
Alarm in Trouble mode.HAS talked with Hawkeye alarm about system.
GENERAL NOTES
JEREMIAH VANDYKE-01/27/2023 @ 14:22 Re-inspection dates are automatically generated 30 days out from the initial
inspection.Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-01/27/2023 @ 14:22 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-01/27/2023 @ 14:22 RE Inspection Fee=$100.00
REINSPECTION DATE
03/01/2023
Printed on 01/30/2023 @ 08:09
Page 2 of 3
CONTACT SIGNATURE
Keri Bentley Contact Refused
Refusal Reason: N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE VG\
Signed on:01/27/2023 @ 14:18 N re\A
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 01/30/2023 @ 08:09
Page 3of3