INSPECTION REPORT
S.A.C'S NEIGHBORHOOD
`c—BAR,2000 HAWTHORNEAVE,BLDG 2000 HAWTHORNEAVE, � / \ '
WATERLOO IA 50702
DETAILS
Inspection Date:01/20/2023 ; Inspection Type:Annual Inspection(1Yr) Inspection Number:8130 I Shift: N/A j Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electric panel.maintain a
minimum of 36"clearance.
FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system and hood fire suppression inspection reports with all discrepancies
corrected.Currently hood cleaning 56 days past due and hood fire suppression 247
days past due.contactor must upload reports online to the compliance engine.
Printed on 01/21/2023 @ 14:51
Page 1 of 3
•
STATUS CODE
DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained
in
with this section and NFPA 10.Exceptions:1.The distance of travel'to reach anrdance
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual fire extinguisher inspection
service.
GENERAL NOTES
JEFF SIEBEL-01/21/2023 @ 14:46 annual inspection$80
REINSPECT/ON DATE
02/08/2023
CONTACT SIGNATURE
Randy Soper
Signed on:01/21/2023 @ 14:48
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:01/21/2023 @ 14:48