INSPECTION REPORT i
TRINITY PRESCHOOL,4535 KIMBALL AVE,BLDG 4535 KIMBALL AVE,WATERLOO IA 50701 4�
DETAILS
Inspection Date:01/31/2023 j Inspection Type:Annual Inspection(1Yr) I Inspection Number:7069 I Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A j Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove temporary barricades when church is
occupied.(blocking exit)
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit light by parish office.
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical panel and fire
alarm panel buy church office.. Maintain a minimum of 36"clearance at all times.
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:provide documentation of dryer vent cleaning to
the outside with signature and date.
Printed on 02/01/2023 @ 09:00
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group I-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers
GENERAL NOTES
JEFF SIEBEL-02/01/2023 @ 08:55 annual inspection$80
JEFF SIEBEL-02/01/2023 @ 08:56 Deliberator requires service indicator is on.Check dates on pads as well.
JEFF SIEBEL-02/01/2023 @ 08:57 Fire drills practiced monthly. Last was 12/20/22 @3:30 with 36 kids.
REINSPECTION DATE
03/03/2023
CONTACT SIGNATURE
Carrie Nieman E'c-i lam/Signed on:02/01/2023 @ 08:57
Printed on 02/01/2023 @ 09:00
Page 2 of 3
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:02/01/2023 @ 08:57 ,'
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 02/01/2023 @ 09:00
Page 3 of 3