COMMERCIAL INSPECTION-2034 LA PORTE RD - 1-24-23 FOR BILLING INQUIRY: (319)291-4323
I_Description I Total Price j
INSPECTION 50,000 $225.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12855 02/15/2023 03/20/2023 2023-00011134 $235.00
Less Prepayment $0.00
Total Due $235.00
City of Waterloo
cc.DG
WATERLOO FIRE RESCUE
INSPECTION REPORT
� l ti
HAMPTON INN&SUITES,2034 LA PORTE RD,BLDG 2034 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date:01/24/2023 I Inspection Type:Annual Inspection(1Yr) j Inspection Number:9469 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL ( Other Inspectors: N/A ; Fee:$235.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments: Remove pallets from stairway landing on 2nd
floor east.
Ira awry°
FAIL 1032.3-Obstructions. A means of egress shall be free from obstructions that would prevent its use,
including the accumulation of snow and ice.
Inspector:JEFF SIEBEL-Comments:Remove obstructions to exit doors:A.Snow
outside main electrical room main exit B.Ashtray blocking stairway exit to outside
stairway 1.Suggest installing permanent sticker stating"Fire Exit Do Not Block".C.
snow blocking back exit from pool.
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit light in pool area to back door.
FAIL 507.5.3-Private fire service Private fire service mains and water tanks shall be periodically inspected,tested and
mains and water tanks. maintained in accordance with NFPA 25 at the following intervals: 1.Private fire
hydrants of all types:Inspection annually and after each operation;flow test and
maintenance annually.2.Fire service main piping: Inspection of exposed,annually;
flow test every 5 years.3.Fire service main piping strainers: Inspection and
maintenance after each use. Records of inspections,testing and maintenance shall
be maintained.
Inspector:JEFF SIEBEL-Comments:provide testing and inspection of private fire
hydrant(red)on North side of building.
Printed on 01/26/2023 @ 10:37
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
S*4"
`r Inspector:JEFF SIEBEL-Comments:remove extension cord from TV in Cedar Valley
Room.A power tap with a reset may be used if properly supported or mounted and
plugged directly into wall.B.remove extension cord from power strip in laundry
office.power strip must plug directly into wall outlet.
FAIL 603.9.4-Prohibited areas. Portable,electric space heaters shall not be operated within 3 feet(914 mm)of any
combustible materials. Portable,electric space heaters shall be operated only in
locations for which they are listed.
'411111 Inspector:JEFF SIEBEL-Comments:Very Hazardous Condition.Remove electric
heater from building.Heater was found running,
g u nmg,plugged into a power step,with
sheets piled beside it and ceiling tile in front of it and near the flammable liquids
storage cabinet with its doors open.
—am
:.
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:provide documentation with signature and date
of dryer vent cleaning to the outside with signature and date for the guest and house
laundry dryers.
Printed on 01/26/2023 @ 10:37
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 704.1 -Maintaining Where required when the building was originally constructed,materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
1 roof/ceiling assemblies.2.joints in smoke barriers.3.Voids at the intersection of a
��,_ _�� horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
..- nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
' 4 intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
s ' intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
-, voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Repair all holes created in sheetrock walls and
ceilings to repair frozen fire sprinkler lines WITH proper permits and inspections
including:A.4th floor electric room by elevator B.electric room by room 431 C.
replace missing ceiling tile by 1st floor ice machine. D.repair ceiling in dining area by
fire sprinkler repair.
e.
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments: Fire doors must completely self-close and latch.
repair the following doors:A. Both elevator fire doors 4th floor. B. Elevator door 3rd
floor.C.repair/replace stair way fire door by room 230.door is sprung and doesn't
seal properly in frame. D. Pool chemical room door E. Pool restroom door. F.Main
1111.11
electrical room door latch missing.G.maintenance office door to corridor. H.All fire
doors must remain closed. Fire doors propped open: 1. Laundry door to corridor 2.
kitchen door to dining.
Printed on 01/26/2023 @ 10:37
Page 3 of 4
STATUS CODE DESCRIPTION
FAIL 903.3.1 -Standards. Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1,unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other
chapters of this code,as applicable.
Inspector:JEFF SIEBEL-Comments:Fire sprinkler lines have frozen and broke,and
have been repaired in several areas including electrical rooms on two floors. Provide
PERMANENT HEAT to these rooms to avoid compromising the fire sprinkler system.
repair walls also)
GENERAL NOTES
JEFF SIEBEL-01/26/2023 @ 10:36 annual inspection$235
REINSPECT/ON DATE
02/14/2023
CONTACT SIGNATURE
Mitch Goodrich-Maintenance •
Signed on:01/25/2023 @ 18:36 I G
r0al1
INSPECTOR SIGNATURE
JEFF SIEBEL
)4
Signed on:01/25/2023 @ 18:35