COMMERCIAL INSPECTION-210 E TOWER PARK DR- 1-25-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
10758 02/15/2023 03/20/2023 2023-00011142 $610.00
Less Prepayment $0.00
Total Due —> $610.00
City of Waterloo
WATERLOO FIRE RESCUE
INSPECTION REPORT °16:j
SAM'S CLUB,210 E TOWER PARK DR,BLDG 210 E TOWER PARK DR, WATERLOO IA 50701 Via'0
DETAILS
Inspection Date:01/25/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:7512 I Shift: N/A I Station: N/A I
Unit: N/A j Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A ( Fee:$610.00
STATUS CODE DESCRIPTION
FAIL 1032.3-Obstructions. A means of egress shall be free from obstructions that would prevent its use,
including the accumulation of snow and ice.
Inspector:JEFF SIEBEL-Comments:middle exit door grocery blocked with snow.
remove snow.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress lights on outside of west exit doors
including tire and receiving.
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit signs hanging by wires:A.NE side
grocery.B.by clorox by middle west exit.
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:A. Provide current annual documentation of
emergency generator annual engine service and load bank testing.B. Provide current
documentation of testing of all emergency egress and exit lights with all
discrepancies corrected with signature and date.
FAIL 507.5.2-Inspection,testing Fire hydrant systems shall be subject to periodic tests as required by the fire code
and maintenance. official.Fire hydrant systems shall be maintained in an operative condition at all
times and shall be repaired where defective.Additions,repairs,alterations and
servicing shall comply with approved standards. Records of tests and required
maintenance shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of repair of broken fire
hydrant that was the basis on a complaint in 11/22.
Printed on 01/26/2023 @ 10:47
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.9.4-Prohibited areas. Portable,electric space heaters shall not be operated within 3 feet(914 mm)of any
combustible materials. Portable,electric space heaters shall be operated only in
locations for which they are listed.
Inspector:JEFF SIEBEL-Comments:remove portable electric heater from customer
care area.
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:replace all missing ceiling tile in pop area.
FAIL 705.2.6-Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested
annually to confirm proper operation and full closure. Records of inspections and
testing shall be maintained.
Inspector:JEFF SIEBEL-Comments:provide current annual fire door drop test
inspection report for tire center fire drop door.
GENERAL NOTES
JEFF SIEBEL-01/25/2023 @ 19:39 annual inspection fee$610
JEFF SIEBEL-01/25/2023 @ 19:42 Survey and maintain storage heights in compliance with fire sprinkler designed heights
of 18'general, 15'tires,and 12'in coolers.
REINSPECTION DATE
02/20/2023
Printed on 01/26/2023 @ 10:47
Page 2 of 3
CONTACT SIGNATURE
Mike Ahmann-Fresh Manager
Signed on:01/26/2023 @ 10:43