COMMERCIAL INSPECTION- 503 SOUTH ST- 1-26-23 FOR BILLING INQUIRY: (319)291-4323
LDescription ( Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12081 02/16/2023 03/20/2023 2023-00011158 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
WATERLOO FIRE RESCUE094)) 4„,..„00
,e‘A
INSPECTION REPORT 1 z 1J
GROUT MUSEUM,503 SOUTH ST,BLD6 503 SOUTH ST,WATERLOO/A 50702
DETAILS
Inspection Date:01/26/2023 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:7225 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1004.9-Posting of occupant Every room or space that is an assembly occupancy shall have the occupant load of
load. the room or space posted in a conspicuous place,near the main exit or exit access
doorway from the room or space,for the intended configurations. Posted signs shall
be of an approved legible permanent design and shall be maintained by the owner or
the owner's authorized agent.
Inspector:JEFF SIEBEL-Comments:move occupancy sign back to banquet room from
classroom
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:provide documentation of testing and repair of all
emergency egress and exit lights in building including the exit light by pioneer hall
door and CBS LA-2A-37 showing failed battery.
FAIL 315.3.2-Means of egress. Combustible materials shall not be stored in exits or enclosures for stairways and
ramps.Combustible materials in the means of egress during construction,
demolition, remodeling or alterations shall comply with Section 3312.3.
Inspector:JEFF SIEBEL-Comments:remove gasoline(snow blower)from exit vestibule
by old fire pumper.
1
Printed on 01/27/2023 @ 12:00
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.2.2-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers
conditionsOpen electrical shall be provided for all switch and electrical outlet boxes.
terminations.
Inspector:JEFF SIEBEL-Comments:properly contain wires on tamper valve on fire
sprinkler wet riser to labeled to old building.
a •
,.4..
'
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3, portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments: Provide annual fire extinguisher service.last 2021
GENERAL NOTES
JEFF SIEBEL-01/27/2023 @ 11:50 annual inspection$80
JEFF SIEBEL-01/27/2023 @ 11:55 Smoke detectors taped over in room next to wood shop was removed during
inspection.Smoke detectors found to be taped over in construction area in lower level.
Advised contractor must be removed every night or when not actively working in area.
JEFF SIEBEL-01/27/2023 @ 11:56
Printed on 01/27/2023 @ 12:00
Page 2 of 3
Y
REINSPECTION DATE
02/21/2023
CONTACT SIGNATURE
Ray Shepard /
Signed on:01/27/2023 @ 11:58 c._ c71
4
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:01/27/2023 @ 11:58