Loading...
HomeMy WebLinkAbout1927 JEFFERSON ST INVOICE DATE DUE DATE INVOICE# TOTAL DUE /%4111■ rat 02/16/2023 03/20/2023 2023-00011169 $80.00 040151te , cPiterloo o Customer#: 24037 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable LA MESILLA BAR AND GRILL 715 Mulberry St 1927 JEFFERSON ST WATERLOO, IA 50703 WATERLOO, IA 50702 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL INSPECTION - 1927 JEFFERSON ST-2-6-23 FOR BILLING INQUIRY: (319)291-4323 Description I Total Price j INSPECTION 2,000 $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 24037 02/16/2023 03/20/2023 2023-00011169 $80.00 Less Prepayment $0.00 Total Due — $80.00 City of Waterloo p�ERCO WATERLOO FIRE RESCUE ac\ --25-] INSPECTION REPORT 2 LA MESILLA BAR AND GRILL,1927JEFFERSON ST,BLDG 1927JEFFERSON ST,WATERLOO/A S0702 4406 DETAILS Inspection Date:02/06/2023 Inspection Type:Annual Inspection(1Yr) I Inspection Number:9612 I Shift: N/A ; Station: N/A I Unit: N/A j Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A I Fee:$80.00 STATUS CODE DESCRIPTION FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The system shall be capable of powering the required load for a duration of not less than 90 minutes. Inspector:JEREMIAH VANDYKE-Comments:2 Exit/Emergency Exit lights tested and failed.Located Back steps and near kitchen. FAIL 603.2.2-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers conditionsOpen electrical shall be provided for all switch and electrical outlet boxes. terminations. Inspector:JEREMIAH VANDYKE-Comments:Cover plates missing that needs replaced.Located 1.on stage floor and 2.Outside above back door. • • Printed on 02/06/2023 @ 15:46 Page 1 of 5 STATUS CODE DESCRIPTION FAIL 606.3.3-Cleaning. Hoods,grease-removal devices,fans,ducts and other appurtenances shall be cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3. Inspector:JEREMIAH VANDYKE-Comments: Hood cleaning is to be completed by licensed contractor and maintained.Hood cleaning report is to be uploaded to Compliance Engine by servicing contractor. FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the inspection,a description of the inspection and when the inspection took place. Records for cleanings shall state the individual and company performing the cleaning and when the cleaning took place.Such records shall be completed after each inspection or cleaning and maintained. Inspector:JEREMIAH VANDYKE-Comments:Hood cleaning is to be completed by licensed contractor and maintained. Hood cleaning report is to be uploaded to Compliance Engine by servicing contractor. FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every system service. six months and after activation of the system. Inspection shall be by qualified individuals,and a certificate of inspection shall be forwarded to the fire code official upon completion. Inspector:JEREMIAH VANDYKE-Comments: Fire suppression system for hood is to be inspected by licensed contractor. Inspection report will need to be uploaded to compliance engine by servicing contractor. Printed on 02/06/2023 @ 15:46 Page 2 of 5 STATUS CODE DESCRIPTION FAIL 906.1 -Where required. Portable fire extinguishers shall be installed in all of the following locations: 1.In new and existing Group A,B,E,F,H,I,M,R-1,R-2,R-4 and S occupancies.Exceptions:1.In Group R-2 occupancies,portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A:10-B:C.2.In Group E occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each classroom is provided with a portable fire extinguisher having " tip la. a minimum rating of 2-A:20-B:C.3. In storage areas of Group S occupancies where N i forklift, powered industrial truck or powered cart operators are the primary �., . 1. d't"N occupants,fixed extinguishers,as specified in NFPA 10,shall not be required where in .11 accordance with all of the following:3.1.Use of vehicle-mounted extinguishers shall be approved by the fire code official.3.2. Each vehicle shall be equipped with a 10- . pound,40A:80B:C extinguisher affixed to the vehicle using a mounting bracket approved by the extinguisher manufacturer or the fire code official for vehicular use. "` 3.3.Not less than two spare extinguishers of equal or greater rating shall be available on-site to replace a discharged extinguisher.3.4.Vehicle operators shall be trained in the proper operation,use and inspection of extinguishers.3.5. Inspections of vehicle- %Y i bl;,`l t' _ mounted extinguishers shall be performed daily.2.Within 30 feet(9144 mm)distance f 1.11 e'', zit!' '' of travel from commercial cooking equipment and from domestic cooking equipment 1/19`1jI'``' ;• . t.i in Group I-1; I-2,Condition 1;and R-2 college dormitory occupancies.3.In areas where flammable or combustible liquids are stored,used or dispensed.4.On each floor of t structures under construction,except Group R-3 occupancies, in accordance with Section 3316.1.5.Where required by the sections indicated in Table 906.1.6.Special- hazard areas,including but not limited to laboratories,computer rooms and generator rooms,where required by the fire code official. Exception: Portable fire extinguishers are not required at normally unmanned Group U occupancy buildings or structures where a portable fire extinguisher suitable to the hazard of the location is provided on the vehicle of visiting personnel. Inspector:JEREMIAH VANDYKE-Comments: 1-A:10-B:C Fire extinguisher's located upstairs and downstairs are past due and need to be serviced by contractor. FAIL 906.4.2-Class K portable fire Where hazard areas include deep fat fryers,listed Class K portable fire extinguishers extinguishers for deep fat shall be provided as follows: 1.For up to four fryers having a maximum cooking fryers. medium capacity of 80 pounds(36.3 kg)each:one Class K portable fire extinguisher of a minimum 1.5-gallon(6 L)capacity.2.For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds(36.3 kg)each:one additional Class K portable fire extinguisher of a minimum 1.5-gallon(6 L)capacity shall be provided.3.For individual fryers exceeding 6 square feet(0.55 m2)in surface area:Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer's recommendations. 4,1 itit -- 1 ,, Inspector:JEREM.IAH VANDYKE-Comments:Class K fire extinguisher is expired and ifflAtIi,tT needs serviced. GENERAL NOTES Printed on 02/06/2023 @ 15:46 Page 3of5 JEREMIAH VANDYKE-02/06/2023 @ 15:37 Discussed with Heather about not using the grill and only having a bar.We discussed if the grill is not to be used that the gas line will have to be capped and possible remove the grill.Heather states she is going to get bids for the Hood cleaning and for the Hood suppression system. JEREMIAH VANDYKE-02/06/2023 @ 15:39 Discussed with Heater about the use of the basement.I advised her that we would need to set up another appointment with the Fire Marshal and Head building official. There are multiple marked Occupancy signs that lead into basement that state"0- zero"occupancy. JEREMIAH VANDYKE-02/06/2023 @ 15:39 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in the event of an emergency at that address.Phone#319-291-2515. JEREMIAH VANDYKE-02/06/2023 @ 15:39 Re-inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections&re-inspections are Monday- Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed the following Monday or Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier re-inspection. JEREMIAH VANDYKE-02/06/2023 @ 15:40 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.- JEREMIAH VANDYKE-02/06/2023 @ 15:40 Inspection Fee=$80.00 REINSPECTION DATE 03/08/2023 CONTACT SIGNATURE Heather Lopez Contact Refused Refusal Reason:N/A emailed. INSPECTOR SIGNATURE JEREMIAH VANDYKE Signed on:02/06/2023 @ 15:31 7 Printed on 02/06/2023 @ 15:46 Page 4 of 5 QUESTIONS ABOUT YOUR INSPECTION? JEREMIAH VANDYKE jeremiah.vandyke@waterloo-ia.org No phone number available Printed on 02/06/2023 @ 15:46 Page 5of5