INSPECTION REPORT
TIRES PLUS,2710 CROSSROADS BLVD,BLDG 2710 CROSSROADS BLVD,WATERLOO IA 50702
440
DETAILS
Inspection Date:12/07/2022 Inspection Type:Annual Inspection(1Yr) I Inspection Number:9097 Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: N/A Fee:$200.00
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Fire alarm in trouble, needs to be
addressed by licensed fire alarm contractor.
OrgOtat
FAIL 509.1 -Identification Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements shall be identified for the use of the
r�
fire department.Approved signs required to identify fire protection equipment and
E_°. ,, t equipment location shall be constructed of durable materials, permanently installed
• and readily visible.
Inspector:JEREMIAH VANDYKE-Comments: Door located in main garage going into
��- tire storage area needs signage. Must have"Sprinkler Riser,FACP,&Main Electrical
panel"for description.
wit
- s
Printed on 12/07/2022 @ 16:21
Page 1 of 3
STATUS CODE DESCRIPTION
FAI L 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments: Egress lights located in shop and in back
parts area tested and failed.
i
;f
f,'
a 4,1
tti
FAIL
604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:All exit lights tested and failed, Exit lights
are also faded and unable to illuminate. Located through out entire building.
ill
v
maxii
y ? Fd
FAIL
si £
Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm need to be inspected by
licensed fire alarm contractor and inspection report uploaded into Compliance
Engine by servicing contractor.
Printed on 12/07/2022 @ 16:21
Page 2of3
GENERAL NOTES
JEREMIAH VANDYKE-12/07/2022 @ 16:18 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-12/07/2022 @ 16:18 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-12/07/2022 @ 16:19 RE-inspection fee:$200.00
REINSPECTION DATE
01/06/2023
CONTACT SIGNATURE
Matt Eschweiler Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE �(�
Signed on: 12/07/2022 @ 16:20 6