COMMERCIAL INSPECTION- 127 JEFFERSON ST- 12-5-22 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23091 12/14/2022 01/20/2023 2023-00011095 $200.00
Less Prepayment $0.00
Total Due -* $200.00
City of Waterloo
3C)9 (
WATERLOO FIRE RESCUE
INSPECTION REPORT
HAB PETROLEUM,127 JEFFERSON ST,BLDG 127JEFFERSON ST,WATERLOO IA 50702 440
DETAILS
Inspection Date: 12/05/2022 Inspection Type:Annual Inspection(1Yr) j Inspection Number:9048 i Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove obstruction(old cooler)from exit path to
back exit.
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit,egress sign above main door.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEFF SIEBEL-Comments:obtain electrical permit and inspections to
properly install light fixture in walk in cooler without permit, replace missing moisture
proof light cover.B.properly mount electrical box for new cooler by rear exit path.
FAIL 605.4.2-Power supply Relocatable power taps shall be directly connected to a permanently installed
receptacle.
Inspector:JEFF SIEBEL-Comments: power strips are daisy chained by lottery
machine. Each power strip must plug directly into wall outlet.
FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEFF SIEBEL-Comments:Appliances with motors produce heat or cooling
must plug directly into power outlet. Relocate power cord.A. live bait cooler.
Printed on 12/05/2022 @ 13:39
Page 1 of 2
STATUS CODE DESCRIPTION
FAI L 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction, including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEFF SIEBEL-Comments: replace missing ceiling tile by bank shot game.
GENERAL NOTES
JEFF SIEBEL-12/05/2022 @ 13:36 re-inspection fee$200
REINSPECTION DATE
01/10/2023
CONTACT SIGNATURE
Mohammad Bhatti ci
Signed on: 12/05/2022 @ 13:36
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 12/05/2022 @ 13:36
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 12/05/2022 @ 13:39