COMMERCIAL INSPECTION- 1825 LA PORTE RD- 10-14-22
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price j
INSPECTION 20,000
$90.00
OCCUPANCY FEE
$10.00
CUSTOMER# I BILLING DATE I DUE DATE INVOICE# CHARGES
23981 11/21/2022 12/26/2022 2023-00011074 023 00011074 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Db CI ki
WATERLOO FIRE RESCUEtvrt
INSPECTION REPORT
BORDERS INN&SUITES 1825 LA PORTE RD,BLDG 1823 LA PORTE RD,WATERLOO LA S0702
DETAILS
Inspection Date: 10/14/2022 I Inspection Type:Annual Inspection(1Yr) Inspection Number:8987 Shift: N/A Station: N/A i
Unit: N/A i Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: N/A I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 404.2.2-Fire safety plans Fire safety plans shall include the following: 1.The procedure for reporting a fire or
other emergency.2.The life safety strategy including the following:2.1. Procedures
for notifying occupants,including areas with a private mode alarm system.2.2.
Procedures for occupants under a defend-in-place response.2.3. Procedures for
evacuating occupants,including those who need evacuation assistance.3.Site plans
indicating the following:3.1.The occupancy assembly point.3.2.The locations of fire
hydrants.3.3.The normal routes of fire department vehicle access.4. Floor plans
identifying the locations of the following:4.1. Exits.4.2. Primary evacuation routes.
4.3.Secondary evacuation routes.4.4.Accessible egress routes.4.4.1.Areas of refuge.
4.4.2. Exterior areas for assisted rescue.4.5. Refuge areas associated with smoke
barriers and horizontal exits.4.6. Manual fire alarm boxes.4.7. Portable fire
extinguishers.4.8.Occupant-use hose stations.4.9. Fire alarm annunciators and
controls.5.A list of major fire hazards associated with the normal use and occupancy
of the premises,including maintenance and housekeeping procedures. 6.
Identification and assignment of personnel responsible for maintenance of systems
and equipment installed to prevent or control fires.7. Identification and assignment
of personnel responsible for maintenance,housekeeping and controlling fuel hazard
sources.
Inspector:JEREMIAH VANDYKE-Comments:Missing safety plans on guest doors in
rooms:#201,#207,#208,209.Will check other occupied rooms for safety plans.
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property.Address identification characters shall
contrast with their background.Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke width of 1/2(12.7 mm).
Where required by the fire code official,address identification shall be provided in
additional approved locations to facilitate emergency response.Where access is by
means of a private road and the building cannot be viewed from the public way,a
monument,pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:Need address identification as described
above.
Printed on 10/14/2022 @ 1 1:30
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL 604.2.12 Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE Comments:All Egress lights tested and failed in west
stair tower.
FAIL
604.2.5 Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments: Exit light tested and failed. Located on
2nd floor hallway near room#202.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEREMIAH VANDYKE Comments: New light covers ordered and on back
,N
ordered for multiple lights in hallways and stairways towers.
bey
%%
FAIL b05.4-Multiplug adapters Multiplug adapters,such as cube adapters, unfused plug strips or any other device
not complying with NFPA 70 shall be prohibited.
Printed an 10/14/2022 @ 11:30
Page 2 of 6
STATUSDESCRIPTION
CODE
g
Inspector:JEREMIAH VANDYKE-Comments: NOT use multi plug extension cords
or power strips for refrigerators, microwaves,CAN coffee makers,or any heat producing
17:14F VW*
appliances.They must be plugged directly into wall outlets.
r
2 fry $.
i
;,-7-,,„-„,,ft::;t=,,,:„,,,_,,i.,:,.,,,,„.,,„\ ,,,
FAIL
605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEREMIAH VANDYKE-Comments:All clothes dryer's exhaust duct system
must be cleaned from the dryer to the outside documented by who and when
serviced. -2021 Code-610.1.2 Maintenance.The lint trap, mechanical and heating
components,and the exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating instructions to prevent the
accumulation of lint or debris that prevents the exhaust of air and products of
combustion.
Printed on 10/14/2022 @ 1 1:30
Page 3 of 6
STATUS CODE DESCRIPTION
FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures, partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
yvy
elements shall be visually inspected by the owner annually and properly repaired,
y0
- restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
y not be required to be visually inspected by the owner unless the concealed space is
� f, accessible by the removal or movement of a panel,access door,ceiling tile or similar
. � movable entry to the space.Openings made therein for the passage of pipes,
h� electrical conduit,wires,ducts,air transfer openings and holes made for any reason= shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
_£. - self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEREMIAH VANDYKE-Comments:Cover and ceiling tiles missing:1.Attic
access 3rd floor.2.2nd floor storage rooms and 1 st floor storage rooms need ceiling
tiles rep
laced.3.Front office back room needs sheetrock replaced.(Fixing water leak
yr , rs and repairing soon)
¢EAVI,ZW yam=
`- may. --¢.
f
s —s
$y
Printed on 10/14/2022 @ 11:30
Page 4 of 6
STATUS CODE DESCRIPTION
FAIL 703.2.3-Door operation Swinging fire doors shall close from the full-open position and latch automatically.
The door closer shall exert enough force to close and latch the door from any
partially open position.
Inspector:JEREMIAH VANDYKE-Comments:Doors did not close and latch: Rooms
#117IJ.3rd floor and 1st floor middle hallway fire doors did not close/latch.
rr�
GENERAL NOTES
JEREMIAH VANDYKE-10/14/2022 @ 11:17 Fire extinguishers serviced/compliant by Proshield Fire on April 2022.
JEREMIAH VANDYKE-10/14/2022 @ 11:24 04/01/2022 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-10/14/2022 @ 11:24 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-10/14/2022 @ 11:25 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-10/14/2022 @ 11:25 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-10/14/2022 @ 11:25 Inspection Fee=$100.00
REINSPECTION DATE
1 1/13/2022
Printed on 10/14/2022 @ 11:30
Page 5 of 6
CONTACT SIGNATURE
Chris Parrill Contact Refused
Refusal Reason: N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 10/14/2022 @ 11:26 J
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 10/14/2022 @ 11:30
Page 6 of 6