COMMERCIAL INSPECTION- 120 JEFFERSON ST- 11-21-22 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4639 11/21/2022 12/26/2022 2023-00011080 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
\I j .UG/y,k.k/
C
WATERLOO FIRE RESCUE \>\ U � 40�eRto 1
INSPECTION REPORT ef. *
�. �
HAWKEYE CHILD CARE CENTER ALC,120 JEFFERSON ST,BLDG 120 JEFFERSON ST., X-\•)`
; \1 -� �,�
WATERLOO ILA50702 ` "`
DETAILS
Inspection Date: 1 1/21/2022 Inspection Type:Annual Inspection(1 Yr) 1 Inspection Number:6869 Shift: N/A i Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL Other Inspectors: N/A %-- .\.),
STATUS CODE DESCRIPTION
FAI 315.3.2-Means of egress Combustible materials shall not be stored in exits or enclosures for stairways and
ramps.
Inspector:JEFF SIEBEL-Comments:remove dumpster from under stairs and exit
corridor to the west.
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
�- 1 -� f� Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
% - Inspector:JEFF SIEBEL-Comments: Remove storage to and around electrical
m equipment including transformers.Only material allowed to be stored in equipment
�� � '� room is materials for equipment. Remove other items.
4
y
ft .
FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEFF SIEBEL-Comments: Provide documentation of dryer vent cleaning to
the outside with signature and date.
GENERAL NOTES
Printed on 1 1/22/2022 @ 10:21
Page 1 of 2
JEFF SIEBEL-11/22/2022 @ 10:17 Tear away Velcro
JEFF SIEBEL-11/22/2022 @ 09:46 annual inspection fee$80
JEFF SIEBEL-11/22/2022 @ 09:48 Fire sprinkler,Fire Alarm, Hood cleaning, Hood fire suppression,and private fire
hydrants all current.
JEFF SIEBEL-11/22/2022 @ 09:48 Fire drills practiced monthly.Last 1 1/10/22
JEFF SIEBEL-11/22/2022 @ 10:16 Recommend review partitioning of main hall. Barrier is tear away but wanted to make
owner aware.
REINSPECTION DATE
12/12/2022
CONTACT SIGNATURE
Nicole Reese 6 teal j
Signed on:11/22/2022 @ 10:18
Iiu
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/22/2022 @ 10:18
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224