HomeMy WebLinkAbout845 W 4TH ST INVOICE DATE DUE DATE INVOICE# TOTAL DUE
i 41 W- 11/21/2022 12/26/2022 2023-00011081 $80.00
_siP
c?ietJoo Ao
Customer#: 23763 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
HOUSE OF HOPE 715 Mulberry St
845 W 4TH ST WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 845 W 4TH ST- 11-21-22 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23763 11/21/2022 12/26/2022 2023-00011081 $80.00
Less Prepayment $0.00
Total Due —> $80.00
City of Waterloo
WATERLOO FIRE RESCUE
INSPECTION REPORT
HOUSE OF HOPE-LEGACY LITTLES,845 W 4TH ST,BLD6 845 W 4TH ST,WATERLOO IA 50702 4
DETAILS
Inspection Date: 11/21/2022 Inspection Type:Annual Inspection(1Yr) ! Inspection Number:7375 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
403.10.2.1.1 -First emergency The first emergency evacuation drill of each school year shall be conducted within 10
evacuation drill days of the beginning of classes.
Inspector:JEREMIAH VANDYKE-Comments: Please send me a recorded of date of fire
drill last completed.
FAI L 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit sign tested and failed. Located in
basement hallway near middle steps near sprinkler riser room.
FAIL, 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction, including,
but not limited to,walls,firestops,shaft enclosures, partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEREMIAH VANDYKE-Comments:Wine/storage room in basement has
propped open door to furnace room.
Printed on 11/21/2022 @ 15:01
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 903.3.1 -Standards Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1,unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other
chapters of this code,as applicable.
Inspector:JEREMIAH VANDYKE-Comments: Deficiency on Compliance Engine:Three
year trip test will be due on dry sprinkler system in warmer weather.Please schedule
with licensed sprinkler contractor for to have corrected in warmer weather.
GENERAL NOTES
JEREMIAH VANDYKE-11/21/2022 @ 14:41 Max#of Children Allowed=4.All children are 2.5 years old or younger.
JEREMIAH VANDYKE-11/21/2022 @ 14:44 01/05/2022 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-11/21/2022 @ 14:44 01/05/2022 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Deficient
JEREMIAH VANDYKE-11/21/2022 @ 14:46 Fire Extinguishers are compliant/serviced by Pro shield in December 2021. Due for
service next month.
JEREMIAH VANDYKE-11/21/2022 @ 14:46 Clothes dryer serviced by Harris Cleaning 7/5/2022.
JEREMIAH VANDYKE-11/21/2022 @ 14:47 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-11/21/2022 @ 14:47 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-11/21/2022 @ 14:47 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-11/21/2022 @ 14:59 Inspection Fee=$80.00-will be scheduling next annual inspection in
October/November 2023.
Printed on 11/21/2022 @ 15:01
Page 2 of 3
GENERAL NOTES
JEREMIAH VANDYKE-11/21/2022 @ 14:58 Please check apartment rooms for any heating devices(refrigerators,microwaves,
coffee makers,and heaters plugged into power strips or extension cords.They must
be plugged directly into wall outlets.
REINSPECTION DATE
12/21/2022
CONTACT SIGNATURE
Chassidi Martin-Royal Legacy Christian Contact Refused
Academy Refusal Reason: N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 11/21/2022 @ 15:00
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 11/21/2022 @ 15:01