COMMERCIAL INSPECTION- 1215 ANSBOROUGH AVE- 9-20-22 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
6293 11/17/2022 12/20/2022 2023-00010988 $80.00
Less Prepayment $0.00
Total Due --> $80.00
City of Waterloo
'...41;\'3
WATERLOO FIRE RESCUE �P�EA�oo
4440
INSPECTION REPORT t
4i
BURGER KING,1215 ANSBOROUGH AVE,BLDG 1215 ANBOROUGH AVE, WATERLOO/A 50701
DETAILS
Inspection Date:09/20/2022 I Inspection Type:Annual Inspection(1Yr) Inspection Number:622 I Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments: Egress light tested and failed. 1.Located
_=- in mens restroom.2.Located in- kitchen area above warming trey.
W
0 * 4
may =
FAIL 604.2.5-Exit signs Emg pwe fgne3
systemer shall ency beo er capableshall be of provid powerindg theorexit required si s as load required for a duration inS ction of not101 less.6.3.thanThe
90 minutes.
IInspector:JEREMIAH VANDYKE-Comments: Exit light tested and failed. Located near
main entrance.
1 ,,
■
i
kaa f
- d f�-
FAIL 605.4.2-Power supply Relocatable power taps shall be directly connected to a permanently installed
receptacle.
Printed on 09/20/2022 @ 15:33
Page 1 of 3
STATUS CODE DESCRIPTION
Inspector:JEREMIAH VANDYKE-Comments: Power tap hanging needs to be secured
` as described above. Located at pickup window area.
•
FA
I L 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
y' elements shall be visually inspected by the owner annually and properly repaired,
6 restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
tom, p p
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
- and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEREMIAH VANDYKE-Comments: Missing ceiling tile above pickup/order
booth area.
FAI 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device, provided that all of the following conditions are met:2.1. Electronic
Novo
X.fe.e 'f,-od , monitoring shall confirm that extinguishers are properly positioned, properly
441� charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
g supervisoryevery years
monitorin devices and su ervisor circuits shall be tested 3 when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3. In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEREMIAH VANDYKE-Comments: Fire extinguishers due for service.
GENERAL NOTES
Printed on 09/20/2022 @ 15:33
Page 2 of 3
JEREMIAH VANDYKE-09/20/2022 @ 15:32 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-09/20/2022 @ 15:33 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-09/20/2022 @ 15:33 Inspection Fee=$80.00
JEREMIAH VANDYKE-09/20/2022 @ 15:33 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
REINSPECTION DATE
10/20/2022
CONTACT SIGNATURE
Andrea Navenma
Signed on:09/20/2022 @ 10:22 \t
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:09/20/2022 @ 10:22
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 09/20/2022 @ 15:33