COMMERCIAL INSPECTION-2710 CROSSROADS BLVD - 11-4-22 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price j
REINSPECTION 2 $150.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
5204 11/17/2022 12/20/2022 2023-00010997 $150.00
Less Prepayment $0.00
Total Due-* $150.00
City of Waterloo
WATERLOO
FIRE RESCUE � s
INSPECTION REPORT
TIRES PLUS,2710 CROSSROADS BLVD,BLDG 2710 CROSSROADS BLVD,WATERLOO IA 50702 440
DETAILS
Inspection Date: 11/04/2022 Inspection Type:Annual Inspection(1Yr) Inspection Number:8922 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$150.00
STATUS CODE DESCRIPTION
FAI L 2015 IFC-Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm in trouble, needs to be
addressed by licensed fire alarm contractor.
it ii
< f
FAIL 509.1 -Identification Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements shall be identified for the use of the
fire department.Approved signs required to identify fire protection equipment and
equipment location shall be constructed of durable materials, permanently installed
tr
g g' and readily visible.
Inspector:JEREMIAH VANDYKE-Comments: Door located in main garage going into
tire storage area needs signage. Must have"Sprinkler Riser, FACP,&Main Electrical
panel"for description.
Printed on 11/04/2022 @ 10:29
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL
604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE Comments: Egress lights located in shop and in back
parts area tested and failed.
t
.
:'4 -> ;- 1,t' ' -_ r
604.2.5 Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
FAIL
90 minutes.
� Inspector:JEREMIAH VANDYKE Comments:All exit lights tested and failed. Exit lights
— are also faded and unable to illuminate. Located through out entire building.
g,FF.
FAIL
Chapter 14 Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE Comments:Fire alarm need to be inspected by
licensed fire alarm contractor and inspection report uploaded into Compliance
� � Engine by servicing contractor.
i
i
Printed on 1 1/04/2022 @ 10:29
Page 2 of 3
GENERAL NOTES
JEREMIAH VANDYKE-11/04/2022 @ 10:25 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-11/04/2022 @ 10:26 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-11/04/2022 @ 10:26 RE-inspection fee:$150.00
REINSPECTION DATE
12/04/2022
CONTACT SIGNATURE
Scott Graham -District Manager Contact Refused
Refusal Reason:N/A
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 11/04/2022 @ 10:25