COMMERCIAL INSPECTION-2820 FALLS AVE - 8-18-22 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22167 11/17/2022 12/20/2022 2023-00011002 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
WATERLOO FIRE RESCUE �P�ER`oo
INSPECTION REPORT
THREE AM/50 S,2820 FALLS AVE,BLDG 2820 FALLS AVE,WATERLOO/A 50701
�C
DETAILS
Inspection Date:08/18/2022 j Inspection Type:Annual Inspection(1Yr) Inspection Number:8329 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: BROCK WELIVER
(RD_ —U)\-10
100
STATUS CODE DESCRIPTION
FAI L 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.2.
Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not accessible to the public. Nesting shall be
allowed provided the nested containers,cylinders or tanks,if dislodged,do not
obstruct the required means of egress.4.Securing of compressed gas containers,
cylinders and tanks to or within a rack,framework,cabinet or similar assembly
designed for such use. Exception:Compressed gas containers,cylinders and tanks in
the process of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments: properly secure ALL compressed gas cylinders
with CHAIN including in basement.
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments: Repair egress light above dishwasher in kitchen.
Suggest mounting fixture to locate the test switch to the bottom for easier monthly
testing.
FAI L 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair exit lights:A.exit egress light above main
door. B. Exit sign above back door at bottom of stairs from the upstairs.
FAI L 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEFF SIEBEL-Comments: Remove oversized bulb from light fixture in
basement employee restroom. Install correctly sized bulb
Printed on 08/18/2022 @ 14:50
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: Provide current semi-annual kitchen hood
exhaust system cleaning report and fire suppression reports with all discrepancies
corrected.Contractor must upload online to the compliance engine.Currently
showing hood cleaning 288 days past due and fire suppression 10 days past due.
FAIL 906.5-Conspicuous location Portable fire extinguishers shall be located in conspicuous locations where they will
be readily accessible and immediately available for use.These locations shall be
along normal paths of travel, unless the fire code official determines that the hazard
posed indicates the need for placement away from normal paths of travel.
Inspector:JEFF SIEBEL-Comments:remove obstructions(refrigerator)to fire
extinguisher.
GENERAL NOTES
BROCK WELIVER-08/18/2022 @ 14:33 A complaint was received by FM Weliver in regards to this property.The complaint was
made by property owner John Hayes.The main items of the complaint were 1)hinge
kits requirements on the kitchen exhaust hood,2)requirements for grease
interceptors in the plumbing,and 3)issues with Commercial Building Inspector Jeff
Siebel performing inspections on his(John Hayes)properties. Item#1:this building
and kitchen hood exhaust system already have a required hinge kit installed.This has
been in place for for some time and is not relevant to the annual fire inspection
performed on this premises. Item#2:the required grease interceptor is not in the
scope of the the annual commercial fire inspection on this property.Any questions or
comments in regards to this issue need to be addressed with the Building Dept.,
specifically the Pluming Inspector. Item#3:The business operating at this location,3
Amigos, has an alcohol license which is regulated by both local and state regulations
which stipulate that an annual fire inspection is to be performed in accordance with
those regulations.When the business submits their required paperwork on an annual
basis,this starts the timely filing process which involves the annual fire inspection.This
process is generally started at the same time every year for this business.The filing of
the required paperwork should serve as an indication that a fire inspection will be
performed in the very near future.John Hayes did speak with FM Weliver about
scheduling the re-inspection of this building/business at 10:00 a.m.on 8/18/2022.John
Hayes did not show up for the re-inspection of the business/building at that time,nor
did he call to cancel or re-schedule. Building Official Greg Ahlhelm and Commercial
Building Inspector Jeff Siebel were both present for the re-inspection of this
business/building and can verify the no-call/no-show of John Hayes.-Brock Weliver
8/18/2022
JEFF SIEBEL-08/18/2022 @ 14:48 re-inspection fee$100
Printed on 08/18/2022 @ 14:50
Page 2 of 3
REINSPECTION DATE
09/08/2022
CONTACT SIGNATURE
Thomas Hernadus
Signed on:08/18/2022 @ 14:49
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/18/2022 @ 14:49
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224