COMMERCIAL INSPECTION- 1604 LA PORTE RD - 11-7-22 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
REINSPECTION 2 $150.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
14658 11/17/2022 12/20/2022 2023-00011012 $150.00
Less Prepayment $0.00
Total Due--> $150.00
City of Waterloo
-\<405`6,
WATERLOO
LOO FIRE RESCUE „oveRcQo
INSPECTION REPORT /A '4 '
CASEY'S GENERAL STORE#2880,1604 LA PORTE RD,BLDG 1604 LA PORTE RD,WATERL000,4%
50702
DETAILSril(-).\ -6°
Inspection Date:11/07/2022 ! Inspection Type:Annual Inspection(1Yr)
pection Number:8988 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: N/A
STATUS CODE
DESCRIPTION
FAIL 1031.3-Obstructions A means of egress shall be free from obstructions that would prevent its use,
including the accumulation of snow and ice.
om exit
Inspector:JEFF SIEBEL-Comments:Remove boxes,path atallp bucets,etc.imesk OPTION:f rSince building
and in front of rear exit door.Maintain clear pa
is a"B"occupation and occupancy load is 31 second exit is not requird.t signs and properly blanaloff
ng
official Greg Ahlhelm grants permission to remove e
with listed covers. However,you must still maintain a minimum of 36"clear path to
and around the electric panel room and panels.
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such
as s oily
ragsremov d and,
tored in a
ignition
listed disposal container.Contents of such
disposed of daily.
Inspector:JEFF SIEBEL-Comments: Provide an approved listed oily waste container
with self closing lid for oily waste.OPTION;Submit a written corporation plan for
proper handling of oily waste materials to prevent spontaneous combustions.
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance
depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical less than t pe width ofervice euiment is the e equipment,er tha 30 inches
(762 mm),the working space shall be
Storage of materials shall not be located within the designated working space.
Exceptions:1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:Maintain minimum distances to and around
electric panels.
FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEFF SIEBEL-Comments:provide documentation of dryer vent cleaning to
the outside of the building.
Printed on 11/08/2022 @ 10:08
Page 1 of 2
GENERAL NOTES
JEFF SIEBEL-11/08/2022 @ 10:08 re-inspection fee$150
REINSPECTION DATE
11/28/2022
CONTACT SIGNATURE
jessica.fisher c 2
Signed on:11/08/2022 @ 10:06
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:11/08/2022 @ 10:06
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 11/08/2022 @ 10:08