HomeMy WebLinkAbout1945 LA PORTE RD -�►'���'� INVOICE DATE DUE DATE INVOICE# TOTAL DUE
!k"g��\(•IrV:- 11/17/2022 12/20/2022 2023-00011014 $100.00
iNage
�T4
Customer#: 13437 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
BAYMONT INN 715 Mulberry St
1945 LA PORTE RD WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1945 LA PORTE RD 10-11-22 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13437 11/17/2022 12/20/2022 2023-00011014 $100.00
Less Prepayment $0.00
Total Due —> $100.00
City of Waterloo
n
WATERLOO FIRE RESCUE - �,PZERtoo
CV/NSPECT/ON REPORT
BAYMONT INN&SUITES,1945 LA PORTE RD,BLDG 1945 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date: 10/11/2022 Inspection Type:Annual Inspection(1Yr) j Inspection Number:6833 Shift: N/A ! Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE 1 Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1103.8-Single-and multiple- Single-and multiple-station smoke alarms shall be installed in existing Group I-1 and
station smoke alarms R occupancies in accordance with Sections 1103.8.1 through 1103.8.3.
Inspector:JEREMIAH VANDYKE-Comments:Smoke alarms tested and failed located
in:#103,#114,#207,#222,and smoke alarm located above guest washer/dryer area
on 1st floor.
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments: Egress light tested and failed located in
hallway near room 204.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEREMIAH VANDYKE-Comments:Open wiring needs to be addressed
located in pool chemical room for light fixture.
Printed on 10/11/2022 @ 14:30
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEREMIAH VANDYKE-Comments:All clothes dryers both guest and hotel's
personal dryers must have exhaust Duct system must be cleaned from the dryer to
the outside DOCUMENTED by who and when serviced.----2021 Code-610.1.2
Maintenance.The lint trap,mechanical and heating components,and the exhaust
duct system of a clothes dryer shall be maintained in accordance with the
manufacturer's operating instructions to prevent the accumulation of lint or debris
that prevents the exhaust of air and products of combustion.
FAIL 703.2-Opening protectives Opening protectives shall be maintained in an operative condition in accordance with
NFPA 80.Where allowed by the fire code official,the application of field-applied labels
associated with the maintenance of opening protectives shall follow the
requirements of the approved third-party certification organization accredited for
listing the opening protective. Fire doors and smoke barrier doors shall not be
blocked or obstructed,or otherwise made inoperable. Fusible links shall be replaced
promptly whenever fused or damaged. Fire door assemblies shall not be modified.
Inspector:JEREMIAH VANDYKE-Comments: 1.Missing fire door going into Electrical
panel room, must be replaced with UL listed certified fire door.2. Door stops must be
removed located on water heater door. Marked fire doors must not be blocked open.
•
sy_
4
v
Printed on 10/11/2022 @ 14:30
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 703.2.3-Door operation Swinging fire doors shall close from the full-open position and latch automatically.
The door closer shall exert enough force to close and latch the door from any
partially open position.
Inspector:JEREMIAH VANDYKE-Comments:Doors did not fully latched located at
rooms:#229 and#210.Explanation above.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E,F, H, I,M, R-1, R-2,R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
�-sj liquids are stored, used or dispensed.4.On each floor of structures under
y yr
construction,except Group R-3 occupancies, in accordance with Section 3315.1. 5.
KSitragfi � Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
i ar including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector:JEREMIAH VANDYKE-Comments: Missing fire extinguisher located on 2nd
floor near room#216.
GENERAL NOTES
JEREMIAH VANDYKE-10/11/2022 @ 14:13 Fire extinguisher serviced/compliant by Hawkeye Fire on March 2022.
JEREMIAH VANDYKE-10/11/2022 @ 14:27 04/22/2022 S-(Annual)Fire Alarm HAWKEYE COMMUNICATION Reviewed Compliant
JEREMIAH VANDYKE-10/11/2022 @ 14:29 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-10/11/2022 @ 14:29 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-10/11/2022 @ 14:29 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-10/11/2022 @ 14:29 Inspection Fee=$100.00
Printed on 10/1 1/2022 @ 14:30
Page 3 of 4
REINSPECTION DATE
11/10/2022
CONTACT SIGNATURE
Chirag Chaudhari Contact Refused
Refusal Reason: N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 10/11/2022 @ 14:27