COMMERCIAL INSPECTION -2034 LA PORTE RD- 10-19-22 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12855 11/17/2022 12/20/2022 2023-00011016 $100.00
Less Prepayment $0.00
Total Due--> $100.00
City of Waterloo
WATERLOO FIRE RESCUE
INSPECTION REPORT .
HAMPTON INN&SUITES,2034 LA PORTE RD,BLDG 2034 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date: 10/19/2022 I Inspection Type:Annual Inspection(1Yr) 1 Inspection Number:7452 Shift: N/A Station: N/A I
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A ; Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1103.8-Single-and multiple- Single-and multiple-station smoke alarms shall be installed in existing Group I-1 and
station smoke alarms R occupancies in accordance with Sections 1103.8.1 through 1103.8.3.
Inspector:JEREMIAH VANDYKE-Comments:Smoke alarms tested and failed in rooms:
#128 and#220.
s
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:According to compliance engine website
a deficiency was found by servicing fire alarm contractor:Answer: Horn Strobe Lobby
East pillar 1st floor did not activate.After corrected by servicing fire alarm contractor
change on compliance engine website by servicing contractor.
Printed on 10/19/2022 @ 11:32
Page 1 of 4
STATUS CODE DESCRIPTION
FAI L 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction, including,
but not limited to,walls,firestops,shaft enclosures, partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space
ace is
accessible by the removal or movement of a panel,access door,ceiling tile or
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEREMIAH VANDYKE-Comments: Broken laundry chute door must self
close and latch. Located on 4th floor.
FAIL 703.2-Opening protectives Opening protectives shall be maintained in an operative condition in accordance with
NFPA 80.Where allowed by the fire code official,the application of field-applied labels
associated with the maintenance of opening protectives shall follow the
requirements of the approved third-party certification organization accredited for
listing the opening protective. Fire doors and smoke barrier doors shall not be
/ blocked or obstructed,or otherwise made inoperable.Fusible links shall be replaced
promptly whenever fused or damaged. Fire door assemblies shall not be modified.
Inspector:JEREMIAH VANDYKE-Comments: Marked fire doors can not be blocked
, gym open. Located in guest laundry room.
FAIL 703.2.3-Door operation Swinging fire doors shall close from the full-open position and latch automatically.
The door closer shall exert enough force to close and latch the door from any
partially open position.
Inspector:JEREMIAH VANDYKE-Comments: Door did not close and latch properly
room#328.
GENERAL NOTES
JEREMIAH VANDYKE-10/19/2022 @ 11:29 08/15/2022 S-(Semi-Annual)Fire Alarm MIDWEST ALARM SERVICES Reviewed Deficient
JEREMIAH VANDYKE-10/19/2022 @ 11:30 06/17/2022 S-(Annual)Fire Sprinkler TRI-STATE AUTOMATIC SPRINKLER,INC. Reviewed
Compliant
Printed on 10/19/2022 @ 11:32
Page 2 of 4
GENERAL NOTES
JEREMIAH VANDYKE-10/19/2022 @ 11:30 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-10/19/2022 @ 11:30 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-10/19/2022 @ 11:30 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-10/19/2022 @ 11:31 Inspection Fee=$100.00
JEREMIAH VANDYKE-10/19/2022 @ 11:11 Fire extinguisher's compliant.
JEREMIAH VANDYKE-10/19/2022 @ 11:19 Dryers serviced by Harris on 3/1/2022.
JEREMIAH VANDYKE-10/19/2022 @ 11:20 Fire drop door laundry chute located in Hotels'Washer and dryer area was serviced by
Christie Door Company 2/27/2022.
REINSPECTION DATE
11/18/2022
CONTACT SIGNATURE
Cayenne Adams-Manager Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE f
Signed on: 10/19/2022 @ 11:32 'J�_/
Printed on 10/19/2022 @ 11:32