COMMERCIAL INSPECTION-2056 LA PORTE RD - 10-19-22 FOR BILLING INQUIRY: (319)291-4323
LDescription ( Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23671 11/17/2022 12/20/2022 2023-00011017 $100.00
Less Prepayment $0.00
Total Due—> $100.00
City of Waterloo
WATERLOO FIRE RESCUE
INSPECTION REPORT
SUBURBAN EXTENDED STAY HOTEL WATERLOO,2056 LA PORTE RD,BLDG 2056 LA PORTE RD,
WATERLOO IA 50702 42460
DETAILS
Inspection Date: 10/19/2022 j Inspection Type:Annual Inspection(1Yr) Inspection Number:6803 I Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1103.8-Single-and multiple- Single-and multiple-station smoke alarms shall be installed in existing Group I-1 and
station smoke alarms R occupancies in accordance with Sections 1103.8.1 through 1103.8.3.
Inspector:JEREMIAH VANDYKE-Comments:Smoke alarms tested and failed in rooms:
#114,#302 living room area,#321,#402 both living room and bedroom alarms.
FAIL 404.2.2-Fire safety plans Fire safety plans shall include the following: 1.The procedure for reporting a fire or
other emergency.2.The life safety strategy including the following:2.1. Procedures
for notifying occupants, including areas with a private mode alarm system.2.2.
Procedures for occupants under a defend-in-place response.2.3. Procedures for
evacuating occupants,including those who need evacuation assistance.3.Site plans
indicating the following:3.1.The occupancy assembly point.3.2.The locations of fire
hydrants.3.3.The normal routes of fire department vehicle access.4. Floor plans
identifying the locations of the following:4.1. Exits.4.2. Primary evacuation routes.
4.3.Secondary evacuation routes.4.4.Accessible egress routes.4.4.1.Areas of refuge
4.4.2. Exterior areas for assisted rescue.4.5. Refuge areas associated with smoke
barriers and horizontal exits.4.6. Manual fire alarm boxes.4.7. Portable fire
extinguishers.4.8.Occupant-use hose stations.4.9. Fire alarm annunciators and
controls.5.A list of major fire hazards associated with the normal use and occupancy
of the premises,including maintenance and housekeeping procedures.6.
Identification and assignment of personnel responsible for maintenance of systems
and equipment installed to prevent or control fires.7. Identification and assignment
of personnel responsible for maintenance,housekeeping and controlling fuel hazard
sources.
Inspector:JEREMIAH VANDYKE-Comments: Missing fire safety plan on door of room
#302.
Printed on 10/19/2022 @ 15:57
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments: Egress lights tested and failed: 1.near
""- sprinkler riser room in hallway.2. 1st floor hallway leading from east stair tower to
outside south parking lot side.3.On east stairway landing between 2nd and 3rd floor.
.2 4.2nd floor storage.5.In hallway across from room#301.6.Egress hallway light on
first floor across from laundry/employee door.
y
v
Wig - .,-
/ ff®
,
i
/
-,,,
j
�` %y _..fir
.fi /f 4 aE
Printed on 10/19/2022 @ 15:57
Page 2 of 5
STATUSDESCRIPTION
CODE
604.2.5-Exit signs Emergency poweg ae3
system shall be er capableshall be of provid poweringdfor the requiredexitsins loadsrequired for a duration inSction of not101 less.6.3.than
90 minutes.
�t % Inspector:JEREMIAH VANDYKE-Comments: Exit signs tested and failed:1.Main lobby.
���/-��`� y _"`
2. Both Exit signs in the pool.
s
g
-;--,-0, ,_, :,,--,, ,- - 4, , ,
,.,...„- -_,-,-_,..., ,,,,, .--,,,„ta
SNulfifSKlpi;
6
3'
16!
---,;- *-;'-,-----''''_St
y � � i 4
y d ¢
r
FAIL, 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEREMIAH VANDYKE-Comments:ALL GUEST and HOTEL'S CLOTHES DRYER
Exhaust Duct system must be cleaned from the dryer to the outside documented by
who and when serviced.----2021 Code-610.1.2 Maintenance.The lint trap,
mechanical and heating components,and the exhaust duct system of a clothes dryer
shall be maintained in accordance with the manufacturer's operating instructions to
prevent the accumulation of lint or debris that prevents the exhaust of air and
products of combustion.
Printed on 10/19/2022 @ 15:57
Page 3of5
STATUS CODE DESCRIPTION
FAIL 703.2-Opening protectives Opening protectives shall be maintained in an operative condition in accordance with
NFPA 80.Where allowed by the fire code official,the application of field-applied labels
associated with the maintenance of opening protectives shall follow the
requirements of the approved third-party certification organization accredited for
Mgr
listing the opening protective. Fire doors and smoke barrier doors shall not be
blocked or obstructed,or otherwise made inoperable. Fusible links shall be replaced
promptly whenever fused or damaged. Fire door assemblies shall not be modified.
Inspector:JEREMIAH VANDYKE-Comments:Broken fire door on 4th floor east stair
tower.
I
•
rWMw -
�G c
j ice`
GENERAL NOTES
JEREMIAH VANDYKE-10/19/2022 @ 15:17 Fire extinguishers compliant
JEREMIAH VANDYKE-10/19/2022 @ 15:54 06/15/2022 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE-10/19/2022 @ 15:55 01/25/2022 S-(Annual)Fire Alarm PROSHIELD FIRE&SECURITY Reviewed Compliant
Printed on 10/19/2022 @ 15:57
Page 4 of 5
GENERAL NOTES
JEREMIAH VANDYKE-10/19/2022 @ 15:55 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-10/19/2022 @ 15:56 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-10/19/2022 @ 15:56 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-10/19/2022 @ 15:56 Inspection Fee=$100.00
REINSPECTION DATE
11/18/2022
CONTACT SIGNATURE
Becky Beerman-Manager Contact Refused
Refusal Reason: N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 10/19/2022 @ 15:52
V �
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 10/19/2022 @ 15:57
Page 5of5