COMMERCIAL INSPECTION-3052 MARNIE AVE- 10-13-22 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price,
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23029 11/17/2022 12/20/2022 2023-00011021 $100.00
Less Prepayment $0.00
Total Due--> $100.00
City of Waterloo
WATERLOO FIRE RESCUE 00
INSPECTION REPORT :t
it
HOWARDJOHNSON,3052 MARNIEAVE,BLDG 3052 MARNIEAVE,WATERLOO/A 50701
DETAILS
Inspection Date: 10/13/2022 j Inspection Type:Annual Inspection(1Yr) j Inspection Number:6749 Shift: N'/A I Station: N/A
Unit: N/A I Lead Inspector:JEREMIAH VANDYKE 1 Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1103.4.9.2.2-Chute intake via Where the intake to chutes is accessed through a chute-intake room,the room shall
a chute-intake room be enclosed with 1-hour fire-resistance-rated construction.Opening protectives for
the intake room shall be in accordance with Section 716 of the International Building
Code and have a fire protection rating of not less than 3/4 hour.Opening protective
for the chute enclosure shall be in accordance with Section 1103.4.9.1.
24
Inspector:JEREMIAH VANDYKE-Comments:2nd floor laundry chute needs to be self
1041 closing.Door is stuck against wall and unable to close.
FA)L 1103.8-Single-and multiple- Single-and multiple-station smoke alarms shall be installed in existing Group I-1 and
station smoke alarms R occupancies in accordance with Sections 1103.8.1 through 1103.8.3.
Inspector:JEREMIAH VANDYKE-Comments:Smoke alarms tested and failed located:
1.West stairwell 2nd floor landing.2.Room:#114 2-smokes,#201,#205,#210,#218,
#220 2-smokes,#225.
Printed on 10/13/2022 @ 16:57
Page 1 of 4
STATUS CODE DESCRIPTION
FAI 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEREMIAH VANDYKE-Comments: 1.Sprinkler system inspection is past
due. Must be serviced by licensed contractor and report uploaded into compliance
engine by servicing contractor.2.There is a deficiency that must be addressed by
licensed contractor.After deficiecny is addressed servicing contractor must change
deficiency in Compliance Engine.----DEFICENCY FOUND by past sprinkler contractor:
Answer: 1968 pendent 212 degree 1/2"standard response 1st floor laundry chute
1968 upright head 286 degree standard response 1/2"2nd floor laundry chute-need
replaced
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEREMIAH VANDYKE-Comments: Located in dining area: 1.Waffle maker
plug has arced cord that needs to be repaired.2.Wall outlet where waffle maker was
plugged in has arc damage to outlet that needs to be repaired with proper outlet.
F IL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
- Inspector:JEREMIAH VANDYKE-Comments: Both Guest and hotel clothes DRYERS
exhaust duct system must be cleaned from the dryer to the outside documented by
who and when serviced.----2021 Code-610.1.2 Maintenance.The lint trap,
mechanical and heating components,and the exhaust duct system of a clothes dryer
shall be maintained in accordance with the manufacturer's operating instructions to
prevent the accumulation of lint or debris that prevents the exhaust of air and
products of combustion.
r,R
Printed on 10/13/2022 @ 16:57
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 605.9-Temporary wiring Temporary wiring for electrical power and lighting installations is allowed for a period
not to exceed 90 days.Temporary wiring methods shall meet the applicable
provisions of NFPA 70. Exception:Temporary wiring for electrical power and lighting
installations is allowed during periods of construction, remodeling, repair or
demolition of buildings,structures,equipment or similar activities.
Inspector:JEREMIAH VANDYKE-Comments:Outdoor lighting can only be used as
temporary as described above.
�f ins
FAIL
o'er
703.2.3-Door operation Swinging fire doors shall close from the full-open position and latch automatically.
The door closer shall exert enough force to close and latch the door from any
partially open position.
Inspector:JEREMIAH VANDYKE-Comments: Room#107 door does not close properly.
GENERAL NOTES
JEREMIAH VANDYKE-10/13/2022 @ 16:20 Fire Extinguisher serviced/compliant by Superior Fire on June 2022.
JEREMIAH VANDYKE-10/13/2022 @ 16:55 09/07/2022 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-10/13/2022 @ 16:56 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-10/13/2022 @ 16:56 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
Printed on 10/13/2022 @ 16:57
Page 3 of 4
GENERAL NOTES
JEREMIAH VANDYKE-10/13/2022 @ 16:56 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-10/13/2022 @ 16:56 Inspection Fee=$100.00
REINSPECTION DATE
11/12/2022
CONTACT SIGNATURE
Arp Patel Contact Refused
Refusal Reason: N/A emailed
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 10/13/2022 @ 16:30
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 10/13/2022 @ 16:57