RENTAL INSPECTION - 1738 FLOWER ST#3 - 12-5-23 FOR BILLING INQUIRY: (319)291-4323
[Description I Total Price J
REINSPECTION FEE 3RD $250.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
10811 12/06/2023 01/10/2024 2024-00000121 $250.00
Less Prepayment $0.00
Total Due —> $250.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
0���0 � ���� ��0��'
mvnnmpmmm��m��m�'m�' �~����� ����*�CUE
INSPECTION REPORT
DOMINIC TAINGEN RENTAl8-PLEX 1738 FLOWER ST, WATERLOO IA So"I
DEvAxLm
Inspection Dare: 12/05/2023 | Inspection Type: Rental inspection [ Inspection Number: 1)375 i Shilft: N/A / Station' N/A �
Unit: N/A | Lead Inspector:BARRYSTRATTON I Other Inspectors: N/A I Fee:$260.00
STATUS CODE ocucn/vr/om
FAIL 1010.1.9 Door operations Except as specifically permitted by this section,egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRvSTRATTON Comments:Door missing on#3
Location: Not Provided
FAIL 1018.1 Genera! Aisles and aisle accessways serving as a portion of the exit access in the means of
egress systern shall comply with the requirements of this section.Aisles or aisle
accessways shall be provided from all occupied portions of the exit access that
contain seats,tables,furnishings, displays and similar-fixtures or equipment.The
minimum width or required capacity of aisles shall be unobstructed. Exception:
Encroachments complying with Section 1005.7.
Inspector: BARRYSTRAlTON Comments:Egress/exit lights still not working
Location: Not Provided
FAIL 1031.2 Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire o''other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means ofegress.
Inspector: BARRYSTRATTON Comments:None
Location: Not Provided
p'`"te"""`z/oseoo�m^o
Page 1orn
STATUS CODE DESCRIPTION
FAIL 1031.7-Emergency escape Required emergency escape and rescue openings shall be maintained in accordance
and rescue openings with the code in effect at the time of construction,and the following: Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars,grilles,grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable from the inside
without the use of a key,tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON-Comments:Broken windows
Location: Not Provided
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property.Address identification characters shall
contrast with their background.Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke width of 1/2(12.7 mm).
Where required by the fire code official,address identification shall be provided in
additional approved locations to facilitate emergency response.Where access is by
means of a private road and the building cannot be viewed from the public way,a
monument,pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector: BARRY STRATTON-Comments: Need numbers on all apartments doors.
Location: Not Provided
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON-Comments:Water damage electric panel in unit#3 will
need replaced
Location: Not Provided
FAIL 901.6-Inspection,testing and Fire detection,alarm,and extinguishing systems,mechanical smoke exhaust
maintenance systems,and smoke and heat vents shall be maintained in an operative condition at
all times,and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected,tested and maintained or
removed.
Inspector: BARRY STRATTON-Comments:Alarm
Location: Not Provided
Printed on 12/0E12023 iga 06.33
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1.In new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed.4. On each floor of structures under
construction,except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON-Comments:None
Location: Not Provided
FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be
multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector:BARRY STRATTON-Comments: None
Location: Not Provided
FAIL R2-Unsafe Equipment Was the presence of unsafe equipment noted during the inspection?Equipment may
include boilers,heating equipment,elevator, moving stairways,electrical wiring,and
flammable liquid containers.(IPMC 108.1.2)
Inspector:BARRY STRATTON-Comments:All units 1-8
Location: Not Provided
FAIL R4- Exterior Property Areas Is the exterior property area maintained in a clean,safe,and sanitary condition?This
includes grading and drainage,sidewalks and driveways,weeds,and pest
infestations.(IPMC 302)
Inspector: BARRY STRATTON-Comments:Debris
Location: Not Provided
FAIL R5-Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state?(IPMC 304)
Inspector: BARRY STRATTON-Comments:Windows and electric service cabinet
Location: Not Provided
FAIL R6- Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Pc need On'I.' J' f. S8
Page 3 of 5
SnmrvS cmoE DESCRIPTION
Inspector: BARRvSTRATTON [ommems: wone
Location:Not Provided
pA|L n6.x. mreriorStruocure' Were any unsafe conditions noted during the interior inspecrion?(|Pxx[3O5.1.1)
Unsafe Conditions
Inspector: BARRvSTR/QTUm Comments:None
Location: Not Provided
AA|L R6.13. Residential Heacin� Are dwellings provided with heating facilities capable of maintaining a room
temperature ofb8F?(|PN1CbU2.2)
Inspector: BARRvSTR/gT0m'Commenrs: wone
Location: Not Provided
FAfL R6.[ Kxechanica| Eqiupmenc Are mechanical appliances properly installed and maintained in good working
condition?(|PK4C6U3.1)
Inspector: BARRYSTR^JTOw Comments: None
Location: Not Provided
GENERAL NOTES
BARRvSTnwQTON 12/85/2023@p06:47 111.8 Prohibited Occupancy.Any occupied structure condemned and placarded by the
code official shall be vacated as ordered by the code official.Any person who shall
occupy placarded premises or shall operate placarded equipment,and ally owner or
owner's authorized agent who shall let anyone occupy a placarded premises or
operate placarded equipment shall be liable foi-the penalties provided by this code.
BARRvSTnATTON 12/05Q023@06:47 111.2 Closing of vacant structures. if the structure is vacant and unfit for human
habitation and occupancy,and is not in clanger of structural collapse,the code official
is authorized to post a placard of condernnation on the premises and order the
structure closed up so as not to be an attractive nuisance. Upon failure of the owner
or owner's authorized agent to close up the premises within the tirne specified in the
order,the code official shall cause the premises to be closed and secured through any
available public agency or by contract or arrangement by private persons and the cost
thereof shall be charged against the real estate upon which the structure is located
and shall be a lien upon such real estate and shall be collected by any other legal
resource.
BAn*vsTnATTON 12/05/2023@06:47 9-7-4 9-7-5:2023 Rental Registration is needed.Still not registered.Building has 8 units
,,,".euon 12,'05V20_a�ou+
Page 4ur5
GENERAL NOTES
BARRY STRATTON-12/05/2023 @ 06:47 Court orders active on listed address.
REINSPECTION DATE
01/02/2024
CONTACT SIGNATURE
Dominic Tangen 61-
Signed on:12/05/2023 @ 06:47
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on:12/05/2023 @ 06:48
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
barry.stratton@waterloo-ia.org
(319)231-9147
F -zed on 12/05/2023 05 43
Page 5 of 5
STATEMENT DATE: 05/17/2023
UNDESIGNATED BALANCE: $0.00
BALANCE DUE: $80.00
CUSTOMER#: 23002 - GUDDI MART
LAST STATEMENT DATE: 05/17/2023
LAST STATEMENT BALANCE: $80.00
GUDDI MART
306 BYRON
WATERLOO, IA 50702
Current Period Activity
Transaction Date Transaction Type Invoice Number _ Transaction Amount
Total Current Period Activity: $0.00
Current Invoice Aging Summary
Invoice No. Invoice Date Description Current 30 Days 60 Days 60+Days
2021-00000295 06/15/2021 COMMERCIAL INSPECTION - 306 BY 0.00 0.00 0.00 80.00
$0.00 $0.00 $0.00 $80.00
IF PAYMENT IS NOT PAID IN FULL BY JUNE 26TH, 2023. THE AMOUNT WILL BE CERTIFIED TO THE PROPERTY TAX