Loading...
HomeMy WebLinkAbout1125-133 DIXON DRIVE ° WA rk` INVOICE DATE DUE DATE INVOICE# TOTAL DUE ( 08/28/2023 09/30/2023 2024-00000064 $250.00 k o /`. ) o Customer#: 24076 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable HUNDRED TICKET VISION LLC 715 Mulberry St PO BOX 56 WATERLOO, IA 50703 WATERLOO, IA 50701 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS RENTAL INSPECTION- 1125-133 DIXON DRIVE - 8-22-23 FOR BILLING INQUIRY: (319)291-4323 LDescription I Total Price REINSPECTION FEE 3RD $250.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 24076 08/28/2023 09/30/2023 2024-00000064 $250.00 Less Prepayment $0.00 Total Due-* $250.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days. .), ky C WATERLOO FIRE RESCUE '` INSPECTION REPORT 101 1125-1133 DIXON DRIVE CONDOMINIUMS BLDG 1133 DIXON DR, ATERLOO IA S0701 (3FIO1v 44Z ° DETAILS Inspection Date:08/22/2023 Inspection Type: Rental Inspection j Inspection Number: 10733 w Shift: N/A I Station: N/A Unit: N/A { Lead Inspector: BARRY STRATTON 1 Other Inspectors: N/A I Fee:$250.00 / (�� f. 5/ STATUS CODE DESCRIPTION FAIL 1008.1 Means of egress Illumination shall be provided in the means of egress in accordance with Section illumination. 1008.2. Under emergency power, means of egress illumination shall comply with Section 1008.3. Inspector: BARRY STRATTON-Comments: Egress lighting does not work.Today's inspections lights still do not work. Location: Not Provided FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied.An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Inspector: BARRY STRATTON-Comments:Front door threshold is obstructing door from closing.Threshold is still not repaired. Rear door is missing door hardware. Location: Not Provided FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical conditions conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official. hazards. Electrical wiring,devices,appliances and other equipment that is modified or damaged and constitutes Conditions that constitute an electrical shock or fire hazard shall be abated not be used. Inspector: BARRY STRATTON-Comments:AC disconnect box on East side of building is hanging by wires. Box needs secured to building.AC disconnect box still hanging from building.Today's inspection one deck screw held box to siding.When checking box it pulled off screw. Box still hanging not secured to building Location: Not Provided Page 1 of 4 STATUS CODE DESCRIPTION FAIL 704.3-Opening protectives. Where openings are required to be protected,opening protectives shall be maintained self-closing or automatic-closing by smoke detection.Existing fusible-link- type automatic door-closing devices are permitted if the fusible link rating does not exceed 135'F(57°C). Inspector:BARRY STRATTON-Comments:Fire doors in open position.Fire doors still left in the open position on todays inspection,may require door closures installed on doors. Location: Not Provided FAIL 901.6-Inspection,testing and Fire detection and alarm systems,emergency alarm systems,gas detection systems, maintenance. fire-extinguishing systems,mechanical smoke exhaust systems and smoke and heat vents protection and life safety systems shall be maintained in an operative condition at all times,and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected,tested and maintained or removed in accordance with Section 901.8. Inspector:BARRY STRATTON-Comments:Alarm need maintenance and testing. Alarm testing still requires tested.Still not done. Location:Not Provided Printed on 08/22/2023 10:24 Page 2 of 4 STATUS CODE DESCRIPTION F.AI L 906.1 -Where required. Portable fire extinguishers shall be installed in all of the following locations:tin new and existing Group A,B, E,F,H,I, M, R-1,R-2, R-4 and S occupancies.Exceptions:1.1n Group R-2 occupancies,portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A:10-B:C.2.1n Group E occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each classroom is provided with a portable fire extinguisher having a minimum rating of 2-A:20-B:C.3.In storage areas of Group S occupancies where forklift,powered industrial truck or powered cart operators are the primary occupants,fixed extinguishers,as specified in NFPA 10,shall not be required where in accordance with all of the following:3.1.Use of vehicle-mounted extinguishers shall be approved by the fire code official.3.2. Each vehicle shall be equipped with a 10- pound,40A:808:C extinguisher affixed to the vehicle using a mounting bracket approved by the extinguisher manufacturer or the fire code official for vehicular use. 3.3.Not less than two spare extinguishers of equal or greater rating shall be available on-site to replace a discharged extinguisher.3.4.Vehicle operators shall be trained in the proper operation,use and inspection of extinguishers.3.5.Inspections of vehicle- mounted extinguishers shall be performed daily.2.Within 30 feet(9144 mm)distance of travel from commercial cooking equipment and from domestic cooking equipment in Group 1-1;1-2,Condition 1;and R-2 college dormitory occupancies.3.1n areas where flammable or combustible liquids are stored,used or dispensed.4.On each floor of structures under construction, except Group R-3 occupancies,in accordance with Section 3316.1.5.Where required by the sections indicated in Table 906.1.6.Special- hazard areas,including but not limited to laboratories,computer rooms and generator rooms,where required by the fire code official. Exception:Portable fire extinguishers are not required at normally unmanned Group U occupancy buildings or structures where a portable fire extinguisher suitable to the hazard of the location is provided on the vehicle of visiting personnel. Inspector:BARRY STRATTON-Comments:Fire Extinguishers need updated.(2021). Fire extinguishers still out of date(2021). Location: Not Provided FAIL R4-Exterior Property Areas Is the exterior property area maintained in a clean,safe,and sanitary condition?This includes grading and drainage,sidewalks and driveways,weeds,and pest infestations.(IPMC 302) Inspector:BARRY STRATTON-Comments:Front concrete slab at door. Busted concrete missing that is under slab.Concrete slab still broken and needs repaired. Location: Not Provided FAIL R6-Interior Structure Has the interior of the structure and equipment inside been maintained in good repair,structurally sound,and in a sanitary condition?(IPMC 305) Inspector:BARRY STRATTON-Comments:Egress lights,fire extinguishers,fire doors, front door threshold. Location: Not Provided GENERAL NOTES Printed on 0812212023 10:24 Page 3 of 4 . . ~ 8ARRYSTRA7TUN 08/22/2023@10:22 AC disconnect still hen�n� |�hr not wmrNngand front�ndingcondhion.��|not corrected. Back door tobuUdingis missing door hardware. R0iNSPECViON DATE _ n0/22/ZO23 CONTACT SIGNATURE Caliber Group Signed on:08/22Y20Z3@10:J3 INSPECTOR SIGNATURE BARRv5TnAlTOw --� Signed on:08/22/2O2]@ 10:23 -- | / QUESTIONS ABOUT YOUR INSPECTION? 8ARRYSTRxTT0m barry.strarzon@wacedoo'ia.org (319)231'9147 Page 4 of 4