RENTAL INSPECTION- 1125-133 DIXON DRIVE - 8-22-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
REINSPECTION FEE 3RD $250.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24076 08/28/2023 09/30/2023 2024-00000064 $250.00
Less Prepayment $0.00
Total Due-* $250.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
.), ky C
WATERLOO FIRE RESCUE '`
INSPECTION REPORT
101
1125-1133 DIXON DRIVE CONDOMINIUMS BLDG 1133 DIXON DR, ATERLOO IA S0701 (3FIO1v 44Z °
DETAILS
Inspection Date:08/22/2023 Inspection Type: Rental Inspection j Inspection Number: 10733 w Shift: N/A I Station: N/A
Unit: N/A { Lead Inspector: BARRY STRATTON 1 Other Inspectors: N/A I Fee:$250.00 / (��
f. 5/
STATUS CODE DESCRIPTION
FAIL 1008.1 Means of egress Illumination shall be provided in the means of egress in accordance with Section
illumination. 1008.2. Under emergency power, means of egress illumination shall comply with
Section 1008.3.
Inspector: BARRY STRATTON-Comments: Egress lighting does not work.Today's
inspections lights still do not work.
Location: Not Provided
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector: BARRY STRATTON-Comments:Front door threshold is obstructing door
from closing.Threshold is still not repaired. Rear door is missing door hardware.
Location: Not Provided
FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical conditions
conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official.
hazards. Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes Conditions that constitute an electrical shock or fire hazard
shall be abated not be used.
Inspector: BARRY STRATTON-Comments:AC disconnect box on East side of building
is hanging by wires. Box needs secured to building.AC disconnect box still hanging
from building.Today's inspection one deck screw held box to siding.When checking
box it pulled off screw. Box still hanging not secured to building
Location: Not Provided
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 704.3-Opening protectives. Where openings are required to be protected,opening protectives shall be
maintained self-closing or automatic-closing by smoke detection.Existing fusible-link-
type automatic door-closing devices are permitted if the fusible link rating does not
exceed 135'F(57°C).
Inspector:BARRY STRATTON-Comments:Fire doors in open position.Fire doors still
left in the open position on todays inspection,may require door closures installed on
doors.
Location: Not Provided
FAIL 901.6-Inspection,testing and Fire detection and alarm systems,emergency alarm systems,gas detection systems,
maintenance. fire-extinguishing systems,mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained in an operative condition
at all times,and shall be replaced or repaired where defective. Nonrequired fire
protection and life safety systems and equipment shall be inspected,tested and
maintained or removed in accordance with Section 901.8.
Inspector:BARRY STRATTON-Comments:Alarm need maintenance and testing.
Alarm testing still requires tested.Still not done.
Location:Not Provided
Printed on 08/22/2023 10:24
Page 2 of 4
STATUS CODE DESCRIPTION
F.AI L 906.1 -Where required. Portable fire extinguishers shall be installed in all of the following locations:tin new
and existing Group A,B, E,F,H,I, M, R-1,R-2, R-4 and S occupancies.Exceptions:1.1n
Group R-2 occupancies,portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.1n Group E occupancies,
portable fire extinguishers shall be required only in locations specified in Items 2
through 6 where each classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C.3.In storage areas of Group S occupancies where
forklift,powered industrial truck or powered cart operators are the primary
occupants,fixed extinguishers,as specified in NFPA 10,shall not be required where in
accordance with all of the following:3.1.Use of vehicle-mounted extinguishers shall
be approved by the fire code official.3.2. Each vehicle shall be equipped with a 10-
pound,40A:808:C extinguisher affixed to the vehicle using a mounting bracket
approved by the extinguisher manufacturer or the fire code official for vehicular use.
3.3.Not less than two spare extinguishers of equal or greater rating shall be available
on-site to replace a discharged extinguisher.3.4.Vehicle operators shall be trained in
the proper operation,use and inspection of extinguishers.3.5.Inspections of vehicle-
mounted extinguishers shall be performed daily.2.Within 30 feet(9144 mm)distance
of travel from commercial cooking equipment and from domestic cooking equipment
in Group 1-1;1-2,Condition 1;and R-2 college dormitory occupancies.3.1n areas where
flammable or combustible liquids are stored,used or dispensed.4.On each floor of
structures under construction, except Group R-3 occupancies,in accordance with
Section 3316.1.5.Where required by the sections indicated in Table 906.1.6.Special-
hazard areas,including but not limited to laboratories,computer rooms and
generator rooms,where required by the fire code official. Exception:Portable fire
extinguishers are not required at normally unmanned Group U occupancy buildings
or structures where a portable fire extinguisher suitable to the hazard of the location
is provided on the vehicle of visiting personnel.
Inspector:BARRY STRATTON-Comments:Fire Extinguishers need updated.(2021).
Fire extinguishers still out of date(2021).
Location: Not Provided
FAIL R4-Exterior Property Areas Is the exterior property area maintained in a clean,safe,and sanitary condition?This
includes grading and drainage,sidewalks and driveways,weeds,and pest
infestations.(IPMC 302)
Inspector:BARRY STRATTON-Comments:Front concrete slab at door. Busted
concrete missing that is under slab.Concrete slab still broken and needs repaired.
Location: Not Provided
FAIL R6-Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Inspector:BARRY STRATTON-Comments:Egress lights,fire extinguishers,fire doors,
front door threshold.
Location: Not Provided
GENERAL NOTES
Printed on 0812212023 10:24
Page 3 of 4
. . ~
8ARRYSTRA7TUN 08/22/2023@10:22 AC disconnect still hen�n� |�hr not wmrNngand front�ndingcondhion.��|not
corrected. Back door tobuUdingis missing door hardware.
R0iNSPECViON DATE _
n0/22/ZO23
CONTACT SIGNATURE
Caliber Group
Signed on:08/22Y20Z3@10:J3
INSPECTOR SIGNATURE
BARRv5TnAlTOw --�
Signed on:08/22/2O2]@ 10:23 -- |
/