SINGLE SPEED BREWING,325 COMMERCIAL ST,BLDG 325 COMMERCIAL ST,WATERLOO IA4,4,0026
S0702
DETAILS
Inspection Date: 11/13/2023 Inspection Type:Annual Inspection(1Yr) 1 Inspection Number:9470 Shift: N/A i Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL i Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
__� - means of egress.
y, r' -� Inspector:JEFF SIEBEL-Comments:remove obstructions to exit door.44"Pathway
�' ;y must be maintained at all times.Unstable storage(stacked)not allowed next to exit
: ., „ path.
I.;k Location:employee entrance
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove obstructions(ladders)from exit path.
Location: Next exit door west of employee exit.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments: East Door out of the coffee shop.
Location:repair egress lights
Printed on 11/15/2023 @ 09:50
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair exit/egress light
Location:South exit past end of bar
FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated.Identified hazardous electrical conditions
conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official.
hazards. Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes Conditions that constitute an electrical shock or fire hazard
shall be abated not be used.
Inspector:JEFF SIEBEL-Comments: Repair blue light on wall.Cover dislodged and
storage against fixture. Maintain proper clearances.
Location: back hall
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electric panel. Maintain a
minimum of 36"clearance at all times.
Location:back hall with blue light.
Printed on 11/15/2023 @ 09:50
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electric panel. Maintain a
minimum of 36"clearance.
Location: By Air compressor
FAIL 603.9.4-Prohibited areas. Portable,electric space heaters shall not be operated within 3 feet(914 mm)of any
combustible materials. Portable,electric space heaters shall be operated only in
locations for which they are listed.
Inspector:JEFF SIEBEL-Comments:remove electric heater from office.
Location:Coffee Shop Office
FAIL 606.3.3-Cleaning. Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3.
Inspector:JEFF SIEBEL-Comments:provide current hood cleaning inspection report
with all discrepancies corrected.Currently 134 days past due.Contractor must
upload report online to the compliance engine.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-11/15/2023 @ 09:23 annual inspection$80
REINSPECTION DATE
12/04/2023
Printed on 11/15/2023 @ 09:50
Page 3 of 4
CONTACT SIGNATURE
Kegan
Signed on:11/15/2023 @ 09:23 �� L
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:11/15/2023 @ 09:23
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224