COMMERCIAL INSPECTION- 1825 LA PORTE RD - 11-16-23 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price J
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24261 11/16/2023 11/20/2023 2024-00000199 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
_
WATERLOO FIRE RESCUE
4: :
INSPECTION REPORT
BOARDERS INN&SUITES,1825 LA PORTE RD,BLDG 1825 LA PORTE RD, WATERLOO IA 50702
DETAILS
Inspection Date: 11/16/2023 Inspection Type:Annual Inspection(1 Yr) Inspection Number:9503 Shift: N/A i Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1103.8-Single-and multiple- Single-and multiple-station smoke alarms shall be installed in existing Group I-1 and
station smoke alarms. R occupancies in accordance with Sections 1103.8.1 through 1103.8.3.
Inspector:JEREMIAH VANDYKE-Comments:Smoke alarms were either missing or not
working.
Location: Rooms 302,306,312,313,314,315,319, 121,205,209,212,215.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress light tested and failed.
Location: East stairway on landing between 1st and 2nd floor.
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Clothes Dryer Exhaust Duct system must
be cleaned from the dryer to the outside DOCUMENTED by who and when serviced.
Location:Guest and Hotels dryers
Printed on 11/16/2023 @ 11:21
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEREMIAH VANDYKE-Comments: 1 &2.Handful of rooms are under
construction with missing sheetrock.3.3rd floor janitors laundry chute room scuddle
hole to attic needs to be closed.
Location: 1.Room#210.2.Hole in wall on 1st,2nd,and 3rd floor in hallway.3.3rd
floor janitors laundry chute room.
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEREMIAH VANDYKE-Comments:Marked fire door not closing or latching
properly.
Location: East stairtower on 1st floor.
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10.Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEREMIAH VANDYKE-Comments:Fire extinguisher in elevator room is past
due and needs to be serviced.
Location: Elevator room on 1st floor.
Printed on 11/16/2023 @ 11:21
Page 2 of 4
GENERAL NOTES
JEREMIAH VANDYKE-11/16/2023 @ 11:20 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-11/16/2023 @ 11:21 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-
1615
JEREMIAH VANDYKE-11/16/2023 @ 11:21 Inspection Fee=$100.00
JEREMIAH VANDYKE-11/16/2023 @ 11:06 03/02/2023 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-11/16/2023 @ 11:07 Fire extinguishers serviced/compliant by Superior Fire March 2023.
JEREMIAH VANDYKE-11/16/2023 @ 11:20 1st floor rooms are under construction.And some rooms are being remodeled due to
water leak.
JEREMIAH VANDYKE-11/16/2023 @ 11:20 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.*****Re inspection fees may be assessed for subsequent re-
inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent
re-inspections.-
REINSPECTION DATE
12/16/2023
CONTACT SIGNATURE
Chris Parrill Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE /)/// 2
gnedon: 11/16/2023@ 11:19 1��
Printed on 11/16/2023 @ 11:21
Page 3 of 4