Loading...
HomeMy WebLinkAbout2343 LOGAN AVE W A T INVOICE DATE DUE DATE INVOICE# TOTAL DUE 11/16/2023 11/20/2023 2024-00000200 $100.00 A./wMAh/I i 7vilN Customer#: 6265 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable MOTEL 6 715 Mulberry St 2343 LOGAN AV WATERLOO, IA 50703 WATERLOO, IA 50703 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL INSPECTION-2343 LOGAN AVE- 11-15-23 FOR BILLING INQUIRY: (319)291-4323 Description Total Price J INSPECTION 20,000 $90.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 6265 11/16/2023 11/20/2023 2024-00000200 $100.00 Less Prepayment $0.00 Total Due-> $100.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days. WATERLOO FIRE RESCUE \946 INSPECTION REPORT MOTEL 6,2343 LOGANAVE,BLDG 2343 LOGANAVE,WATERLOO IA 50703 DETAILS Inspection Date: 11/15/2023 j Inspection Type:Annual Inspection(1Yr) Inspection Number:9863 Shift: N/A Station: N/A Unit: N/A ( Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$100.00 STATUS CODE DESCRIPTION FAIL 1103.8-Single-and multiple- Single-and multiple-station smoke alarms shall be installed in existing Group I-1 and station smoke alarms. R occupancies in accordance with Sections 1103.8.1 through 1103.8.3. Inspector:JEREMIAH VANDYKE-Comments: Missing or non working smoke alarms. Location: Rooms#211,210,219,and 224. FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance illumination. with Sections 1008.3 and 1104.5.1. Inspector:JEREMIAH VANDYKE-Comments: Egress lights tested and failed. Location: Pool area both Egress lights. FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The system shall be capable of powering the required load for a duration of not less than 90 minutes. Inspector:JEREMIAH VANDYKE-Comments:Exits lights tested and failed. Location: 1.Pool area.2.Floor exit light near room#206.3.Near room#115. FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated.Identified hazardous electrical conditions conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official. hazards. Electrical wiring,devices,appliances and other equipment that is modified or damaged and constitutes Conditions that constitute an electrical shock or fire hazard shall be abated not be used. Inspector:JEREMIAH VANDYKE-Comments:Tipped over rusted lamp being used as light source. Location: Pool Boiler room. FAIL 603.2.2-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers conditionsOpen electrical shall be provided for all switch and electrical outlet boxes. terminations. Inspector:JEREMIAH VANDYKE-Comments: Plates needed on open junction boxes. Printed on 11/15/2023 @ 15:11 Page 1 of 3 STATUS CODE DESCRIPTION Location: 1.Storage office room.2.Pool Boiler room.3.Room#223. FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code. Inspector:JEREMIAH VANDYKE-Comments:Orange extension cord and power strip need to be removed. Location: Pool boiler room. FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.2.Thirty-day inspections shall not be required and maintenance shall be allowed to be once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device,provided that all of the following conditions are met:2.1.Electronic monitoring shall confirm that extinguishers are properly positioned,properly charged and unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices and supervisory circuits shall be tested every 3 years when extinguisher maintenance is performed.2.5.A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be permitted to be located at staff locations. Inspector:JEREMIAH VANDYKE-Comments:All fire extinguishers are past due and need to be serviced. Location: Not Provided GENERAL NOTES JEREMIAH VANDYKE-11/15/2023 @ 14:56 01/16/2023 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC. Reviewed Compliant JEREMIAH VANDYKE-11/15/2023 @ 14:56 01/16/2023 S-5 Year Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC. Reviewed Compliant JEREMIAH VANDYKE-11/15/2023 @ 14:57 11/21/2022 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant JEREMIAH VANDYKE-11/15/2023 @ 14:57 Clothes dryers serviced and cleaned in house last completed 11/1/2023. Printed on 11/15/2023 @ 15:11 Page 2of3 GENERAL NOTES JEREMIAH VANDYKE-11/15/2023 @ 15:10 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in the event of an emergency at that address.Phone#319-291-2515. JEREMIAH VANDYKE-11/15/2023 @ 15:11 Inspection Fee=$100.00 JEREMIAH VANDYKE-11/15/2023 @ 15:10 Re-inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections&re-inspections are Monday- Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed the following Monday or Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier re-inspection.*****Re inspection fees may be assessed for subsequent re- inspections. Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.- JEREMIAH VANDYKE-11/15/2023 @ 15:10 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883- 1615 REINSPECTION DATE 12/15/2023 CONTACT SIGNATURE Gina Abrahamson Reason for not collecting a signature: NA INSPECTOR SIGNATURE JEREMIAH VANDYKE Signed on: 11/15/2023 @ 15:11 J\ • QUESTIONS A/OUT YOUR INSPECTION? JEREMIAH VANDYKE jeremiah.vandyke@waterloo-ia.org No phone number available Printed on 11/15/2023 @ 15:11 Page 3 of 3