COMMERCIAL PROPERTY- 1945 LA PORTE RD- 11-16-23 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13437 12/06/2023 01/10/2024 2024-00000211 $100.00
Less Prepayment $0.00
Total Due—4 $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE „moo
INSPECTION REPORT
BAYMONT INN&SUITES,1945 IA PORTE RD,BLDG 1945 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date: 11/16/2023 Inspection Type:Annual Inspection(1Yr) 1 Inspection Number:9692 I Shift: N/A j Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE ; Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit lights tested and failed.
Location: 1.Near room#231.2.Near room#100.
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:None
Location:Not Provided
FAIL 315.3.3-Equipment rooms. Combustible material shall not be stored in boiler rooms,mechanical rooms,
electrical equipment rooms or in fire command centers as specified in Section
508.1.5.
Inspector:JEREMIAH VANDYKE-Comments:I removed the door stop.The door is
marked fire door and must be closed and latched at all times with no storage allowed
in there.Please remove tape from door latch.
Location:Water heater room by front desk and laundry room.
Printed on 11/16/2023 @ 15:35
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEREMIAH VANDYKE-Comments:Refridgerators,microwaves,and coffee
makers must be plugged directly into wall outlets and NOT into cube adapters,
extension cords,or power strips.
Location: Rooms I inspected with cube adapters:#209,205,229,225,109, 111.
e
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEREMIAH VANDYKE-Comments:Refridgerators,microwaves,and coffee
makers must be plugged directly into wall outlets and NOT into cube adapters,
extension cords,or power strips.
Location: Rooms I inspected with orange extension cord:#226,224,223,222,221,
219,218,217,216,215,214,211,203,100,101,107,117,119, 120,and 123.
Printed on 1 1/16/2023 @ 15:35
Page 2 of 5
STATUSDESCRIPTION
LODE
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
- ---4---t-- *-i--7--_tti,-:!, r damage or physical impact.Extension cords shall be used only with portable
-
appliances.Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEREMIAH VANDYKE-Comments: Refridgerators,microwaves,and coffee
4
makers must be plugged directly into wall outlets and NOT into cube adapters,
extension cords,or power strips.
Location:Rooms I inspected with orange extension cord:#226,224,223,222,221,
219,218,217,216,215,214,211,203,100,101,107,117,119,120,and 123.
iliiiii._ - t
FAIL 603.8-Temporary wiring. Temporary The use of temporary wiring for electrical power and lighting installations
shall not exceed is allowed for a period not to exceed of 90 days.Temporary wiring
methods shall meet the applicable provisions of NFPA 70.Exception:Temporary
wiring for electrical power and lighting installations is allowed complying with the
applicable provisions of NFPA 70 is permitted during periods of construction,
remodeling,repair or demolition of buildings,structures,equipment or similar
T activities.
s Inspector:JEREMIAH VANDYKE-Comments: Refridgerators,microwaves,and coffee
makers must be plugged directly into wall outlets and NOT into cube adapters,
extension cords,or power strips.
Location: Rooms I inspected with orange extension cord:#226,224,223,222,221,
219,218,217,216,215,214,211,203,100,101,107,117,119,120,and 123.
Printed on 11/16/2023 @ 15:35
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Clothes Dryer Exhaust Duct system must
be cleaned from the dryer to the outside DOCUMENTED by who and when serviced.
Location:All clothes dryers.
GENERAL NOTES
JEREMIAH VANDYKE-11/16/2023 @ 11:47 04/24/2023 S-(Annual)Fire Alarm HAWKEYE COMMUNICATION Reviewed Compliant
JEREMIAH VANDYKE-11/16/2023 @ 11:48 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.*****Re inspection fees may be assessed for subsequent re-
inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE-11/16/2023 @ 11:48 Inspection Fee=$100.00
JEREMIAH VANDYKE-11/16/2023 @ 11:48 Fire extinguishers serviced by Hawkeye fire and safety June 2023.
JEREMIAH VANDYKE-11/16/2023 @ 11:48 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-11/16/2023 @ 11:48 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-
1615
REINSPECTION DATE
12/16/2023
CONTACT SIGNATURE
Chirag Chaudhari Reason for not collecting a signature:NA
Printed on 11/16/2023 @ 15:35
Page 4 of 5
INSPECTOR SIENATURE
JEREMIAH VANDYKE 7,./3
Signed on:11/16/2023 @ 12:19
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 1 1/16/2023 C 15:35