COMMERCIAL PROPERTY-2035 E MITCHELL AVE- 11-22-23 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price,
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23182 12/06/2023 01/10/2024 2024-00000216 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE �P1ER`oo
INSPECTION REPORT i
KING STAR,2035 E MITCHELL AVE,BLDG 2035 E MITCHELL AVE,WATERLOO LA 50702
DETAILS
Inspection Date: 11/22/2023 j Inspection Type:Annual Inspection(1Yr) I Inspection Number: 11461 I Shift: N/A I Station: N/A I
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit light above main door
Location: Main door
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:Repair exit light above door.
Location:Side door to the west
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if dislodged,do not obstruct
the required means of egress.4.Securing of compressed gas containers,cylinders
and tanks to or within a rack,framework,cabinet or similar assembly designed for
such use. Exception:Compressed gas containers,cylinders and tanks in the process
of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:properly secure compressed gas cylinder with
chain.
Location: Not Provided
f.* Printed on 1 1/28/2023 @ 12:41
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical conditions
conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official.
hazards. Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes Conditions that constitute an electrical shock or fire hazard
shall be abated not be used.
Inspector:JEFF SIEBEL-Comments:remove or properly contain all electrical wiring
►. outside in front soffit in accordance with electrical codes.
Location: Front soffit
*IOW f
FAIL 603.5.3-Installation. Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector:JEFF SIEBEL-Comments:properly mount power strip by gas controller in
back room. May not hang by cords.
Location: Near gas controller in back room.
Printed on 11/28/2023 @ 12:41
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 906.1 -Where required. Portable fire extinguishers shall be installed in all of the following locations:1.In new
and existing Group A,B,E,F,H,I,M,R-1, R-2,R-4 and S occupancies.Exceptions: 1.In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.In Group E occupancies,
portable fire extinguishers shall be required only in locations specified in Items 2
through 6 where each classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C.3. In storage areas of Group S occupancies where
forklift,powered industrial truck or powered cart operators are the primary
occupants,fixed extinguishers,as specified in NFPA 10,shall not be required where in
accordance with all of the following:3.1. Use of vehicle-mounted extinguishers shall
be approved by the fire code official.3.2. Each vehicle shall be equipped with a 10-
pound,40A:80B:C extinguisher affixed to the vehicle using a mounting bracket
approved by the extinguisher manufacturer or the fire code official for vehicular use.
3.3. Not less than two spare extinguishers of equal or greater rating shall be available
on-site to replace a discharged extinguisher.3.4.Vehicle operators shall be trained in
the proper operation,use and inspection of extinguishers.3.5.Inspections of vehicle-
mounted extinguishers shall be performed daily.2.Within 30 feet(9144 mm)distance
of travel from commercial cooking equipment and from domestic cooking equipment
in Group 1-1; 1-2,Condition 1;and R-2 college dormitory occupancies.3.In areas where
flammable or combustible liquids are stored,used or dispensed.4.On each floor of
structures under construction,except Group R-3 occupancies,in accordance with
Section 3316.1.5.Where required by the sections indicated in Table 906.1.6.Special-
hazard areas,including but not limited to laboratories,computer rooms and
generator rooms,where required by the fire code official. Exception: Portable fire
extinguishers are not required at normally unmanned Group U occupancy buildings
or structures where a portable fire extinguisher suitable to the hazard of the location
is provided on the vehicle of visiting personnel.
Inspector:JEFF SIEBEL-Comments:replace missing fire extinguisher next to side
door.
Location:near side door
Printed on 1 1/28/2023 @ 12:41
Page 3of5
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10.Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:Provide annual service for all fire extinguishers.
expired 2020
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-11/28/2023 @ 12:36 annual inspection$80
REINSPECTION DATE
12/13/2023
CONTACT SIGNATURE
Muhammad Bhatti )(cc,. c/ l—L
Signed on:11/28/2023 @ 12:40
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/28/2023 @ 12:40
Printed on 11/28/2023 @ 12:41
Page 4 of 5
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 11/28/2023 @ 12:41
Page 5 of 5