COMMERCIAL PROPERTY-228 E 4TH ST- 11-22-23 FOR BILLING INQUIRY: (319)291-4323
lDescription I Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
14048 12/06/2023 01/10/2024 2024-00000220 $80.00
Less Prepayment $0.00
Total Due--f $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
�p1ER(oo
INSPECTION REPORT I ,
SCREAMING EAGLE BAR&GRILL,228 E 4TH ST,BLDG 228 E 4TH ST,WATERLOO IA 50703
DETAILS
Inspection Date: 11/22/2023 ; Inspection Type:Annual Inspection(1Yr) ; Inspection Number:9675 I Shift: N/A I Station: N/A j
Unit: N/A ; Lead Inspector:JEFF SIEBEL ! Other Inspectors: N/A ; Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening The force for pushing or pulling open interior swinging egress doors,other than fire
force Forces to unlatch and doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
open doors. required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following: 1.Where door hardware operates by push or
pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).
2.Where door hardware operates by rotation,the operational force to unlatch the
door shall not exceed 28 inch-pounds(315 N-cm).The force to open doors shall
comply with the following: 1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force for pushing or pulling
open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding
doors or folding doors,and doors required to be fire rated,the door shall require
not more than a 30-pound(133 N)force to be set in motion and shall move to a full-
open position when subjected to not more than a 15-pound(67 N)force.
Inspector:JEFF SIEBEL-Comments:Repair exit door.Must unlatch and swing to full
open with less than 15#force.
Location: Rear basement to outside alley
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light.
Location:Above North side door
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light.
Location:Above Miller GD sign by stage
FAIL 606.3.3-Cleaning. Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3.
Printed on 11/28/2023 @ 11:36
Page 1 of 3
s
STATUS CODE DESCRIPTION
Inspector:JEFF SIEBEL-Comments:provide documentation of kitchen hood cleaning
-' J with all discrepancies corrected.Currently 13 days past due.Contractor must upload
. online to the compliance engine. Install grease filters correctly to allow for grease
-' \ 74-I Iit
drainage to tray and catch pan.
- Location:kitchen hood exhaust cleaning and filters
I �
FAIL 705.2-Inspection and Opening protectives in fire-resistance-rated assemblies shall be inspected and
maintenance. maintained in accordance with NFPA 80.Opening protectives in smoke barriers shall
be inspected and maintained in accordance with NFPA 80 and NFPA 105.Openings in
smoke partitions shall be inspected and maintained in accordance with NFPA 105.
Fire doors and smoke and draft control doors shall not be blocked,obstructed,or
otherwise made inoperable. Fusible links shall be replaced promptly whenever fused
f or damaged.Opening protectives and smoke and draft control doors shall not be
4{ modified.
Inspector:JEFF SIEBEL-Comments:REPEAT VIOLATION Remove garbage can from
_- "„'g r obstructing fire door.
tow"
-101 : Location: Fire door between kitchen and bar
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:Provide current annual fire alarm inspection
report with all discrepancies corrected.Currently 125 days past due.Contractor must
upload online to the compliance engine.
Location: Fire Alarm
GENERAL NOTES
JEFF SIEBEL-11/28/2023 @ 11:22 Annual inspection$80
JEFF SIEBEL-11/28/2023 @ 11:24 Fire extinguishers due in December.
JEFF SIEBEL-11/28/2023 @ 11:23 Kitchen hood fire suppression due 12/13/23
REINSPECTION DATE
12/13/2023
Printed on 11/28/2023 @ 1 1:36
Page 2of3