COMMERCIAL INSPECTION-3251 GREYHOUND DR- 10-27-23 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price J
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23977 11/15/2023 12/20/2023 2024-00000175 $100.00
Less Prepayment $0.00
Total Due—> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
n
WATERLOO FIRE RESCUE 0
INSPECTION REPORT 4:0D
LOVES TIRE SHOP,3251 GREYHOUND DR,BLDG 3251 GREYHOUND DR.,WATERLOO/A 50702
DETAILS
Inspection Date: 10/27/2023 Inspection Type:Annual Inspection(1Yr) ( Inspection Number: 11179 Shift: N/A I Station: N/A
Unit: N/A ; Lead Inspector:JEFF SIEBEL Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light
Location:top of loft stairs
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light
Location: NW corner of building on fire wall
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings, nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:remove extension cord attached to wall up over
door.
Location: North west corner
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:Door must completely self-close and latch.
Location:Walk thru fire door in 3 hour fire wall
Printed on 10/30/2023 @ 09:10
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments: Provide annual fire alarm testing.Contractor
must post online to the compliance engine.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-10/09/2023 @ 11:05 Fire extinguishers due this month.
JEFF SIEBEL-10/09/2023 @ 11:05 Fire door drop test completed 8/24/23
JEFF SIEBEL-10/30/2023 @ 08:44 re-inspection fee$100
REINSPECTION DATE
11/17/2023
CONTACT SIGNATURE
Jim Wellner ru ci y
Signed on:10/30/2023 @ 08:51
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 10/30/2023 @ 08:51