Loading...
HomeMy WebLinkAbout315 OAKRIDGE RD O V W A INVOICE DATE DUE DATE INVOICE# TOTAL DUE e 11/15/2023 12/20/2023 2024-00000182 $80.00 0 Customer#: 21987 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable KINGDOM KIDS 715 Mulberry St 315 OAK RIDGE RD WATERLOO, IA 50703 WATERLOO,IA 50702 Amount Enclosed.. DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL INSPECTION- 315 OAKRIDGE RD - 10-19-23 FOR BILLING INQUIRY: (319)291-4323 L Description I Total Price INSPECTION 2,000 $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 21987 11/15/2023 12/20/2023 2024-00000182 $80.00 Less Prepayment $0.00 Total Due—> $80.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days. WATERLOO FIRE RESCUEIt 4(30 4,TERto. INSPECTION REPORT / \ 41 KINGDOM KIDS,315 OAKRIDGE RD,BLDG 315 OAKRIDGE RD,WATERLOO/A S0701 DETAILS Inspection Date: 10/19/2023 Inspection Type:Annual Inspection(1Yr) ; Inspection Number:9947 I Shift: N/A i Station: N/A I Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A ' Fee:$80.00 STATUS CODE DESCRIPTION FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied.An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Inspector:JEREMIAH VANDYKE-Comments:Storage is to be cleared leading to the _ outside in marked exit paths. Location:ALL EXITS leading out of classrooms X4 to the outside. f 4 .� <441 44* gip_, iRz ....kill , .` n/ FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance illumination. with Sections 1008.3 and 1104.5.1. Inspector:JEREMIAH VANDYKE-Comments: Egress lights tested and failed. Location: 1.Kitchen above stove.2.Peaceful playroom/storage. FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The system shall be capable of powering the required load for a duration of not less than 90 minutes. Inspector:JEREMIAH VANDYKE-Comments:Exit lights tested and failed.Have electician check ALL exit lights when repairing others. Location: 1.Room Peaceful Playroom/storage.2.Infant room Printed on 10/19/2023 @ 15:22 Page 1 of 3 STATUS CODE DESCRIPTION FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and shall be listed and labeled in accordance with UL 817.Extension cords and flexible cordsshall not be affixed to structures,extended through walls,ceilings or floors,or under doors or floor coverings,nor shall such cords be subject to environmental damage or physical impact.Extension cords shall be used only with portable appliances. Extension cords marked for indoor use shall not be used outdoors. Inspector:JEREMIAH VANDYKE-Comments:Yellow extension cord being used as permanent wiring. Please remove. Location:Office FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a clothes dryer shall be maintained in accordance with the manufacturer's operating instructions to prevent the accumulation of lint or debris that prevents the exhaust of air and products of combustion. Inspector:JEREMIAH VANDYKE-Comments:Clothes Dryer Exhaust Duct system must be cleaned from the dryer to the outside DOCUMENTED by who and when serviced Location:Clothes dryer EAi k_ R2-Unsafe Equipment Was the presence of unsafe equipment noted during the inspection?Equipment may include boilers,heating equipment,elevator,moving stairways,electrical wiring,and flammable liquid containers.(IPMC 108.1.2) Inspector:JEREMIAH VANDYKE-Comments:Need Iowa Division of Labor certificate of inspection completed by the State. Location: Boiler GENERAL NOTES JEREMIAH VANDYKE-10/19/2023 @ 15:03 Fire exitinguisher serviced by Proshield April 2023. JEREMIAH VANDYKE-10/19/2023 @ 15:04 Fire Drill completed and recorded 8/28/2023 JEREMIAH VANDYKE-10/19/2023 @ 15:05 04/06/2023 S-(Annual)Fire Alarm PROSHIELD FIRE&SECURITY Reviewed Compliant Printed on 10/19/2023 @ 15:22 Page 2of3 GENERAL NOTES JEREMIAH VANDYKE-10/19/2023 @ 15:20 Re-inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections&re-inspections are Monday- Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed the following Monday or Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier re-inspection.*****Re inspection fees may be assessed for subsequent re- inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.- JEREMIAH VANDYKE-10/19/2023 @ 15:20 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883- 1615 JEREMIAH VANDYKE-10/19/2023 @ 15:20 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in the event of an emergency at that address. Phone#319-291-2515. JEREMIAH VANDYKE-10/19/2023 @ 15:20 Inspection Fee=$80.00 REINSPECT/ON DATE 11/18/2023 CONTACT SIGNATURE Faith Garcia Reason for not collecting a signature: NA INSPECTOR SIGNATURE JEREMIAH VANDYKE Signed on: 10/19/2023 @ 15:21 1 ./7A/1 111 QUESTIONS AMOUT YOUR INSPECTION? JEREMIAH VANDYKE jeremiah.vandyke@waterloo-ia.org No phone number available Printed on 10/19/2023 @ 15:22 Page 3 of 3