COMMERCIAL INSPECTION-2060 SOVIA DR- 11-2-23 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22533 11/15/2023 12/20/2023 2024-00000186 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE s,p(ER(°°
INSPECTION REPORT % ti2•
DIAMOND NAILS,2060 SOVIA DR,BLDG 2060 SOVIA DR-STE 108,WATERLOO IA 50702 G2
DETAILS
Inspection Date: 11/02/2023 I Inspection Type:Annual Inspection(1Yr) I Inspection Number: 11371 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Inspector:JEFF SIEBEL-Comments:Obtain permits and inspections:A. Plumbing for
Kitchen sink,additional wash machine. B.Obtain permit and inspections for electrical
for additional dryer.C.Obtain final inspections for additional dryer vents and kitchen
hood.
Location: Not Provided
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:Remove obstructions,especially flammable and
combustibles. Items in exit path must not impede exit path and be stable.All
flammables must be stored in a flammable liquids storage cabinet.
Location:rear hall way to restrooms
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:Repair exit light
Location: Main front door
Printed on 1 1/07/2023 @ 09:53
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances.Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:remove extension cord
Location: Round table front SE corner
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:remove extension cord to appliances. Must plug
directly into wall outlet.
Location: Massage room
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings, nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances.Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments: Remove extension cord to air compressor.Air
compressor must plug directly into permanent wall outlet.
Location:room after the massage room
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:Fire door must completely self-close and latch.
Location: Fire exit door by back restrooms to exit path
Printed on 11/07/2023 @ 09:53
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10.Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual fire extinguisher service for all fire
extinguishers.
Location: Front SE corner and rear break area.
GENERAL NOTES
JEFF SIEBEL-11/06/2023 @ 09:11 annual inspection$80
JEFF SIEBEL-11/07/2023 @ 09:49 previous inspection was incomplete and rolled into this new annual.$200 re-
inspection fees will resume at next inspection if ALL discrepancies are not corrected.
JEFF SIEBEL-11/07/2023 @ 08:32
JEFF SIEBEL-11/07/2023 @ 08:33
REINSPECTION DATE
12/04/2023
CONTACT SIGNATURE
Kevin Phan
Signed on:11/07/2023 @ 09:51