COMMERCIAL INSPECTION-2060 SOVIA DR- 10-31-23 FOR BILLING INQUIRY: (319)291-4323
[Description Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4750 11/15/2023 12/20/2023 2024-00000187 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE - as
INSPECTION REPORT t' i
CARLOS O'KELLY'S,2060 SOVIA DR,BLDG 2060 SOVIA DR-STE 104,WATERLOO IA 50702 \c\�
DETAILS
Inspection Date: 10/31/2023 1 Inspection Type:Annual Inspection(1Yr) ; Inspection Number:9383 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIv 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments: Remove obstructions from ext path. Maintain a
Minimum 36"clear path.All storage must be stable
sr
Location: Kitchen exit to back hall
,111115 Alf
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light.
Location:outside main front door
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Repair egress lights in upper ceiling of dining
room and provide documentation of inspections and repairs with signature and
date. May be emailed to inspector.
Location:Upper ceiling in dining room
FAIL 606.3.3.2-Grease If during the inspection it is found that hoods,grease-removal devices,fans,ducts or
accumulation. other appurtenances have an accumulation of grease,such components shall be
cleaned in accordance with ANSI/IKECA C10.
Printed on 11/01/2023 @ 09:45
Page 1 of 3
•
STATUS CODE DESCRIPTION
Inspector:JEFF SIEBEL-Comments:Clean filters above cooking appliances. Filters
have grease accumulating and dripping.
Location:filters above cooking equipment
FAIL 903.3.3-Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance with
the applicable automatic sprinkler system standard that is being used.Automatic
sprinklers shall be installed in or under covered kiosks,displays,booths,concession
stands or equipment that exceeds 4 feet(1219 mm)in width.Not less than a 3-foot
(914 mm)clearance shall be maintained between automatic sprinklers and the top of
piles of combustible fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with Section 904.
Inspector:JEFF SIEBEL-Comments:Clean or replace fires sprinkler heads th
at p p are
loaded with grease.
Location: kitchen by conveyer oven
_
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:Provide current annual fire alarm inspection
report with all discrepancies corrected.Currently 61 days past due.Contractor must
upload report online to the compliance engine.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-11/01/2023 @ 09:26 annual inspection$80
Printed on 11/01/2023 @ 09:45
Page 2of3
REINSPECTION DATE
11/27/2023
CONTACT SIGNATURE
Sarah Bullerman
Signed on: 11/01/2023 @ 09:43 G7
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/01/2023 @ 09:43
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 11/01/2023 @ 09:45