COMMERCIAL INSPECTION- 120 SUMNER ST- 11-7-23 FOR BILLING INQUIRY: (319)291-4323
[Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23516 11/15/2023 12/20/2023 2024-00000189 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE4Pp,00
INSPECTION REPORT
CLUB LEGACY,120 SUMNER ST,BLDG 120 SUMNER ST,WATERLOO IA 50703
4t.o.
DETAILS
Inspection Date: 11/07/2023 Inspection Type:Annual Inspection(1Yr) j Inspection Number:9523 Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1010.2.9-Panic and fire exit Swinging doors serving a Group H occupancy and swinging doors serving rooms or
hardware. spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be
provided with a latch or lock other than panic hardware or fire exit hardware.
Exceptions: 1.A main exit of a Group A occupancy shall be permitted to have locking
devices in accordance with Section 1010.2.4, Item 2 3.2.Doors provided with panic
hardware or fire exit hardware and serving a Group A or E occupancy shall be
permitted to be electrically locked in accordance with Section 1010.2.12 or 1010.2.11.
3. Exit access doors serving occupied exterior areas shall be permitted to be locked in
accordance with Section 1010.2.4, Item 8.4.Courtrooms shall be permitted to be
locked in accordance with Section 1010.2.13, Item 3.Electrical rooms with equipment
rated 1,200 amperes or more and over 6 feet(1829 mm)wide,and that contain
overcurrent devices,switching devices or control devices with exit or exit access
doors,shall be equipped with panic hardware or fire exit hardware.The doors shall
swing in the direction of egress travel.
Inspector:JEFF SIEBEL-Comments:Repair or Replace broken panic hardware in back
bar area.
Location: Not Provided
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:Provide currently serviced fire extinguisher
mounted 4"to 5'above the floor in an accessible place.One in each bar area.
Location: Not Provided
Printed on 11/08/2023 @ 08:14
Page 1 of 2
STATUS CODE DESCRIPTION
F AIL 906.7-Hangers and brackets. Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied.Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:fire extinguishers must be mounted 4"to 5'
above the floor.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-11/08/2023 @ 08:13 annual inspection$80
REINSPECTION DATE
12/07/2023
CONTACT SIGNATURE
Trice Scott
Signed on: 11/08/2023 @ 08:03 2Pr/ Zt7
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/08/2023 @ 08:11