COMMERCIAL INSPECTION- 504 SYCAMORE ST- 10-16-23 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23251 11/15/2023 12/20/2023 2024-00000190 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
4p1ERC00
INSPECTION REPORTt f
ARIZ,504 SYCAMORE ST,BLDG 504 SYCAMORE ST,WATERLOO/A 50703
DETAILS
Inspection Date: 10/16/2023 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:9292 ; Shift: N/A I Station: N/A j
Unit: N/A j Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Inspector:JEFF SIEBEL-Comments:Contact contractor to Obtain HVAC and electrical
permits for new furnace installed in ceiling
Location:front bar area
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Replace missing ceiling or install fire sprinkler
coverage above ceiling.
Location:front bar area
Printed on 10/17/2023 @ 09:03
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:Fire extinguishers due for annual service
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-10/17/2023 @ 09:01 oven removed from power strip during inspection.
JEFF SIEBEL-10/17/2023 @ 09:00 annual inspection fee$80
REINSPECTION DATE
11/06/2023
CONTACT SIGNATURE
Helen Redding
Signed on:10/17/2023 @ 08:59
(' /( V
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 10/17/2023 @ 09:00
Printed on 10/17/2023 @ 09:03
Page 2 of 3
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 10/17/2023 @ 09:03
Page 3of3