COMMERCIAL INSPECTION - 844 W 4TH ST- 10-25-23 FOR BILLING INQUIRY: (319)291-4323
Description ( Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3309 11/15/2023 12/20/2023 2024-00000192 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE �,P�ERLoo
INSPECTION REPORT t/'
TRI-COUNTY CHILD&FAMILY DEVELOPMENT COUNCIL,840-844 W 4TH ST,BLDG 844 W 4TH �
ST,WATERLOO IA 50702
DETAILS
Inspection Date: 10/25/2023 j Inspection Type:Annual Inspection(1Yr) ; Inspection Number:1422 j Shift: N/A Station: N/A I
Unit: N/A Lead Inspector:JEREMIAH VANDYKE ; Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening The force for pushing or pulling open interior swinging egress doors,other than fire
force Forces to unlatch and doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
open doors. required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door hardware operates by push or
pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).
2.Where door hardware operates by rotation,the operational force to unlatch the
door shall not exceed 28 inch-pounds(315 N-cm).The force to open doors shall
comply with the following: 1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force for pushing or pulling
open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding
doors or folding doors,and doors required to be fire rated,the door shall require
not more than a 30-pound(133 N)force to be set in motion and shall move to a full-
open position when subjected to not more than a 15-pound(67 N)force.
Inspector:JEREMIAH VANDYKE-Comments:Marked Exit door extremely hard to
open.
Location:844 building leading out to alleyway from stairtower.
FAIL 109.1 -Maintenance of Where any device,equipment,system,condition,arrangement,level of protection,or
safeguards. any other feature is required for compliance with the provisions of this code,or
otherwise installed,such device,equipment,system,condition,arrangement, level of
protection,or other feature shall thereafter be continuously maintained in
accordance with this code and applicable referenced standards.
Inspector:JEREMIAH VANDYKE-Comments:State of Iowa Divison of Labor certificated
needed for Boilers.
Location: Building 844 basement boiler room.
Printed on 10/25/2023 @ 17:03
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL 1103.9-Carbon monoxide Carbon monoxide alarms detection shall be installed in existing dwelling units and
alarmsdetection. sleeping units Group I-1,1-2, 1-4 and R occupancies and in classrooms in Group E
occupancies where those units include any of the conditions identified in Sections
915.1.2 through 915.1.6.The carbon monoxide alarms shall be installed in the
locations specified in Section 915.2 and the installation shall be in accordance with
Section 915.4.Exceptions: 1.Carbon monoxide alarms are permitted to be solely
battery operated where the code that was in effect at the time of construction did
not require carbon monoxide detectors to be provided.2.Carbon monoxide alarms
are permitted to be solely battery operated in dwelling units that are not served from
a commercial power source.3.A carbon monoxide detection system in accordance
with Section 915.5 shall be an acceptable alternative to carbon monoxide alarms.
Inspector:JEREMIAH VANDYKE-Comments:Carbon Monoxide alarm on ceiling tested
and failed.Contact Hawkeye Alarm to address alarm
Location: Basement room#111.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:All EGRESS emergency lights in hallways,
bathrooms,and classrooms were tested and failed. Need to repair or replace.
Location:840 and 844 basements.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Exit and egress lights were not working.
Might have a breaker tripped. Must contact electrician to address.
Location: 1st floor hallway leading to dentist office near doors#5 and#2.
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit and egress lights were not working.
Might have a breaker tripped. Must contact electrician to address.
Location: 1st floor hallway leading to dentist office near doors#5 and#2.
Printed on 10/25/2023 @ 17:03
Page 2of6
STATUS CODE DESCRIPTION
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:Are these in service for emergency and
41*_. exit lights?Need to contact electrician to see if they are in service?If not they will
e need to be removed.
Location:Building 840-Stand by power panels found in basement mechanical rooms
and near room#213 upstairs.
FAIL 315.3.3-Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms,
electrical equipment rooms or in fire command centers as specified in Section
508.1.5.
Inspector:JEREMIAH VANDYKE-Comments:Storage in basement mechanical rooms
need to be cleared of all storage.
Location: Basement Mechanical rooms.
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEREMIAH VANDYKE-Comments: Deficiency Found:Answer:no key for
padlock-did not cycle elevator equipment room control valve.CONTACT blackhawk
sprinkler.
Location:840 Basement room elevator mechanical room. Deficeincy noted on
compliance engine website.
V
I
I ,
Printed on 10/25/2023 @ 17:03
Page 3 of 6
STATUS CODE DESCRIPTION
FA L 603.2.2-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers
conditionsOpen electrical shall be provided for all switch and electrical outlet boxes.
terminations.
Inspector:JEREMIAH VANDYKE-Comments:Open tamper box and electrical box.
Needs to be addressed by Hawkeye Alarm.
Location:844 basement Sprinkler riser room/elevator room.
re, :14
{
FAIL 705.2-Inspection and Opening protectives in fire-resistance-rated assemblies shall be inspected and
maintenance. maintained in accordance with NFPA 80.Opening protectives in smoke barriers shall
be inspected and maintained in accordance with NFPA 80 and NFPA 105.Openings in
smoke partitions shall be inspected and maintained in accordance with NFPA 105.
Fire doors and smoke and draft control doors shall not be blocked,obstructed,or
otherwise made inoperable. Fusible links shall be replaced promptly whenever fused
or damaged.Opening protectives and smoke and draft control doors shall not be
modified.
Inspector:JEREMIAH VANDYKE-Comments:Missing ceiling tiles.
Location: Basement Room#111
GENERAL NOTES
JEREMIAH VANDYKE-10/25/2023 @ 15:36 KITCHEN CLASS-K Fire Extinguisher serviced by Hawkeye Fire&Safety December 2022.
Due in December 2022
JEREMIAH VANDYKE-10/25/2023 @ 15:41 06/29/2023 S-Kitchen Hood Suppression HAWKEYE FIRE&SAFETY CO. Reviewed
Compliant
JEREMIAH VANDYKE-10/25/2023 @ 15:42 Currently have 60 enrolled, up to 120 total on state certificate.
JEREMIAH VANDYKE-10/25/2023 @ 16:25 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.*****Re inspection fees may be assessed for subsequent re-
inspections. Re-inspection fees start at$100,then$150,and$200 for all subsequent
re-inspections.-
Printed on 10/25/2023 @ 17:03
Page 4 of 6
GENERAL NOTES
JEREMIAH VANDYKE-10/25/2023 @ 16:25 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-
1615
JEREMIAH VANDYKE-10/25/2023 @ 16:25 Inspection Fee=$80.00
JEREMIAH VANDYKE-10/25/2023 @ 15:37 Fire Extinguishers serviced by Hawkeye Fire&Safety August 2023.
JEREMIAH VANDYKE-10/25/2023 @ 15:41 09/05/2023 L-(Annual)Kitchen Exhaust HARRIS CLEANING SERVICE AND AH Reviewed
Compliant
JEREMIAH VANDYKE-10/25/2023 @ 15:41 02/23/2023 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant Compliant
JEREMIAH VANDYKE-10/25/2023 @ 15:41 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant Compliant
JEREMIAH VANDYKE-10/25/2023 @ 15:42 Fire Drill recorded and completed 9/29/2023.
JEREMIAH VANDYKE-10/25/2023 @ 16:25 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
REINSPECTION DATE
11/24/2023
CONTACT SIGNATURE
Pauline Jones Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 10/25/2023 @ 16:29
Printed on 10/25/2023 @ 17:03
Page 5of6
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 10/25/2023 @ 17:03
Page 6 of 6