COMMERCIAL INSPECTION- 1350 KATOSKI DR- 9-19-23 FOR BILLING INQUIRY: (319)291-4323
lDescription I Total Price I
INSPECTION 50,000 $225.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3608 09/28/2023 10/31/2023 2024-00000123 $235.00
Less Prepayment $0.00
Total Due— $235.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
�ptERj�O
INSPECTION REPORT
CENTRAL MIDDLE SCHOOL,1350 KATOSKI DR,BLDG 1350 KATOSKI DR,WATERLOO IA 50701 4,40
DETAILS
Inspection Date:09/19/2023 Inspection Type:Biennial Inspection(2yrs) i Inspection Number:6757 ; Shift: N/A Station: N/A
Unit: N/A j Lead Inspector:BROCK WELIVER Other Inspectors:JEREMIAH VANDYKE Fee:$235.00
STATUS CODE DESCRIPTION
FAIL 1010.1 -Doors. Means Doors in the means of egress shall comply with the requirements of Sections
1010.1.1 through 1010.3.4.Exterior exit doors shall meet also comply with the
requirements of this section.Doors serving a Section 1022.2.Gates in the means of
egress shall comply with the requirements of Sections 1010.4 and 1010.4.1.Turnstiles
in the means of egress system shall meet comply with the requirements of this
section and Section 1022.2.Doors Sections 1010.5 through 1010.5.4. Doors,gates
and turnstiles provided for egress purposes in numbers greater than required by
this code shall meet comply with the requirements of this section.Doors in the
Means means of egress doors shall be readily distinguishable from the adjacent
construction and finishes such that the doors are easily recognizable as doors.
Mirrors or similar reflecting materials shall not be used on means of egress doors.
Means of egress doors shall not be concealed by curtains,drapes,decorations or
similar materials.
Inspector: BROCK WELIVER-Comments:Exit door from class room was hidden
behind a curtain to prevent students from leaving the room. Exit doors need to be
available for use at anytime and must be readily distinguishable.
Location:WCC 319
FAIL 1010.1.3-Door opening The force for pushing or pulling open interior swinging egress doors,other than fire
force Forces to unlatch and doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
open doors. required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following: 1.Where door hardware operates by push or
pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).
2.Where door hardware operates by rotation,the operational force to unlatch the
door shall not exceed 28 inch-pounds(315 N-cm).The force to open doors shall
comply with the following:1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force for pushing or pulling
open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding
doors or folding doors,and doors required to be fire rated,the door shall require
not more than a 30-pound(133 N)force to be set in motion and shall move to a full-
open position when subjected to not more than a 15-pound(67 N)force.
Inspector:BROCK WELIVER-Comments: Roof access door is very hard to open
Location: Roof access by WCC 203
Printed on 09/20/2023 @ 16:38
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.5.3-Installation. Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector: BROCK WELIVER-Comments: Daisy chained electrical cords behind
refrigerator
Location:210 A
FAIL 705.2.3-Hold-open devices Hold-open devices and automatic door closers,where provided,shall be maintained.
and closers. During the period that such device is out of service for repairs,the door it operates
shall remain in the closed position.
Inspector:BROCK WELIVER-Comments:No violation-doors are wired for electronic
hold open devices,there are no magnets installed on the doors-check with your
installing contactor to finish placing the magnets on the doors.
Location:Stairway 2nd floor WCC&Doors at top of stairs at Door 19
GENERAL NOTES
BROCK WELIVER-09/20/2023 @ 15:59 Fire sprinkler:current,report is located in TCE,no deficiencies noted.*5 year sprinkler
inspection is due 5/15/2024
BROCK WELIVER-09/20/2023 @ 16:09 Fire Extinguishers:current,serviced by Superior Fire Protection,June 2023
BROCK WELIVER-09/20/2023 @ 16:36 Inspection fee=$235
BROCK WELIVER-09/20/2023 @ 16:01 Fire Alarm:past due,renewal date was for 8/2/2023.Contact your alarm contractor for
annual inspection/testing/maintenance.*Ongoing construction could be the cause in
the delay
BROCK WELIVER-09/20/2023 @ 16:07 Hood suppression:current,last serviced 8/15/2023,report is in TCE, no deficiencies
noted
BROCK WELIVER-09/20/2023 @ 16:07 Hood cleaning:current,last serviced 3/16/2023,report is in TCE, no deficiencies noted
BROCK WELIVER-09/20/2023 @ 16:08 Private hydrants:current,last serviced 6/22/2023.Report is in TCE,no deficiencies
noted.
Printed on 09/20/2023 @ 16:38
Page 2 of 3
GENERAL NOTES
BROCK WELIVER-09/20/2023 @ 16:29 This inspection also includes the WCC Expansion.The construction areas on the
southern portion of the middle school are not included on this inspection.The gym,
pool,auditorium,commons area,and kitchen were all inspected as part of the
construction project prior to the start of the school year.The construction project is
scheduled to be completed and turned over during winter break and will be inspected
prior to the building being completed for turn over.
BROCK WELIVER-09/20/2023 @ 16:36 Invoice Contact/Zach Kelly/319-404-8085
BROCK WELIVER-09/20/2023 @ 16:32 Stage Curtains: last treated 2020
NEXT INSPECTION DATE
09/19/2025
CONTACT SIGNATURE
Zach Kelly Reason for not collecting a signature:Contact refused
Refusal Reason:N/A
INSPECTOR SIGNATURE
BROCK WELIVER
Signed on:09/20/2023 @ 16:37