HomeMy WebLinkAbout1425 KIMBALL AVE O T INVOICE DATE DUE DATE INVOICE# TOTAL DUE
09/28/2023 10/31/2023 2024-00000124 $80.00
., f/avt,. f c
. Illl�rrrrrr�rr jrYiir.
Customer#: 23982 Please Make Check Payable and Remit To:
City of Waterloo
A TTN: City Clerk/Accounts Receivable
NEW LIFE CENTER 715 Mulberry St
1423 KIMBALL AVE WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1425 KIMBALL AVE- 9-18-23 FOR BILLING INQUIRY: (319)291-4323
LDescription ( Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23982 09/28/2023 10/31/2023 2024-00000124 $80.00
Less Prepayment $0.00
Total Due - $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
x\L,,,4e
3�PTERC�
WATERLOO FIRE RESCUE
INSPECTION REPORT ,
NEW LIFE CENTER,1425 KIMBALL AVE,BLDO 139 E MIT ELL AVE,WATERLOO IA 50702 f11
4740,
•
DETAILS �t
Inspection Date:09/18/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:8920 j Shift: N/A i Station: N/A
Unit: N/A I Lead Inspector:JEREMIAH VANDYKE 1 Other Inspectors:BROCK WELIVER Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress light tested and failed.
Location: In basement of New Life in the"Tornado area safety room".
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:In basement of Church in main hall above
the sets of double doors the Exit light failed.
Location:Basement of Church.
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm panel in trouble mode,they
have made contact with fire alarm contractor to address panel.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-09/18/2023 @ 08:21 Fire Extinguisher serviced by Pro Shield in April 2023.
JEREMIAH VANDYKE-09/18/2023 @ 08:23 08/17/2023 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed
Printed on 09/18/2023 @ 08:29
Page 1 of 2
GENERAL NOTES
JEREMIAH VANDYKE-09/18/2023 @ 08:23 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.*****Re inspection fees may be assessed for subsequent re-
inspections. Re-inspection fees start at$100,then$150,and$200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE-09/18/2023 @ 08:23 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-
1615
JEREMIAH VANDYKE-09/18/2023 @ 08:24 Inspection Fee=$80.00
REINSPECTION DATE
10/18/2023
CONTACT SIGNATURE
Steve Lathrop Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:09/18/2023 @ 08:28D k._
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 09/18/2023 @ 08:29
Page 2of2