COMMERCIAL INSPECTION- 1805 LA PORTE RD - 9-25-23 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price J
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24210 09/28/2023 10/31/2023 2024-00000130 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\(-1x.c3
WATERLOO FIRE RESCUE
INSPECTION REPORT4:01
DOMINO'S PIZZA,1805 LA PORTE RD,BLDG 1805 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date:09/25/2023 ; Inspection Type:Annual Inspection(1Yr) I Inspection Number: 10988 Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:Mike Heerkes I Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:Mike Heerkes-Comments:remove obstructions to electric panel. Maintain
a minimum of 36"clearance at all times.9/25/23-Still need all items removed in front
of panel
Location:back room
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:Mike Heerkes-Comments:Provide documentation of clothes dryer vent
cleaning to the outside of the building with a signature and date.
Location: Dryer
Printed on 09/26/2023 @ 10:41
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector: Mike Heerkes-Comments:Fire extinguishers not serviced since 2020.
Provide annual service.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-08/31/2023 @ 08:39 annual inspection fee$80
Mike Heerkes-09/26/2023 @ 10:37 Re-inspection fee$100.00
REINSPECTION DATE
10/26/2023
CONTACT SIGNATURE
Justin Wince DMA I
Signed on:09/26/2023 @ 10:39
INSPECTOR SIGNATURE
Mike Heerkes
Signed on:09/26/2023 @ 10:38 411
Printed on 09/26/2023 @ 10:41