COMMERCIAL INSPECTION - 120 JEFFERSON ST- 10-19-23 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4639 11/01/2023 12/10/2023 2024-00000140 $80.00
Less Prepayment $0.00
Total Due—* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
�� SERA
WATERLOO FIRE RESCUE v,vs, �P
INSPECTION REPORT ,at
HAWK EYE CHILD CARE CENTER MC,120 JEFFERSON ST,BLDG 120 JEFFERSON ST.,
WATERLOO/A S0702 42ZZOk
DETAILS
Inspection Date: 10/19/2023 i Inspection Type:Annual Inspection(1Yr) ,,.tospection Number:9330 Shift: N/A Station: N/A I
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening The force for pushing or pulling open interior swinging egress doors,other than fire
force Forces to unlatch and doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
open doors. required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following: 1.Where door hardware operates by push or
pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).
2.Where door hardware operates by rotation,the operational force to unlatch the
door shall not exceed 28 inch-pounds(315 N-cm).The force to open doors shall
comply with the following: 1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force for pushing or pulling
open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding
doors or folding doors,and doors required to be fire rated,the door shall require
not more than a 30-pound(133 N)force to be set in motion and shall move to a full-
open position when subjected to not more than a 15-pound(67 N)force.
Inspector:JEFF SIEBEL-Comments: Repair north egress gate,must open with less
than 15#force.
Location: North Gate of North outdoor play area.
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of emergency egress and
exit lights including central battery station with all discrepancies corrected.
Location: Not Provided
Printed on 10/20/2023 @ 09:27
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials, permanently installed and readily visible.
Inspector:JEFF SIEBEL-Comments: Install permanent signage on outside of door
"FACP"or Fire Department Remote Command Center.
Location: Door 11 ,west side of building to Fire Department Remote Command
Center.
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Replace misplaced ceiling tile
Location: Laundry Room
GENERAL NOTES
JEFF SIEBEL-10/20/2023 @ 09:21 Fire drills completed monthly.Last 9/7/23 with 28 children.
JEFF SIEBEL-10/20/2023 @ 09:22 Dryer vent cleaning by Chris Shannon 10/5/23
JEFF SIEBEL-10/20/2023 @ 09:06 Annual inspection fee$80
REINSPECTION DATE
11/16/2023
Printed on 10/20/2023 @ 09:27
Page 2 of 3
CONTACT SIGNATURE
Sarah Errthum
Signed on: 10/20/2023 @ 09:20 L
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 10/20/2023 @ 09:20