HomeMy WebLinkAbout 900 LAPORTE RD W q T� INVOICE DATE DUE DATE INVOICE# TOTAL DUE
ate %
• �� - 11/01/2023 12/10/2023 2024-00000144 $80.00
• llllfs 0
Ll/ sirrn'fs`tti;r •
) V.=_ 0
ww.wr 3))
Customer#: 13176 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CHAPALA 715 Mulberry St
900 LA PORTE RD WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION -900 LA PORTE RD - 9-27-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13176 11/01/2023 12/10/2023 2024-00000144 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
f \ �y
WATERLOO FIRE RESCUE * VV[[ p,SERIO
a
ev,
INSPECTION REPORT
CHAPALAS,900 LA PORTE RD,BLDG 900 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date:09/27/2023 j Inspection Type:Annual Inspection(1Yr) i Inspection Number:9144 Shift: N/A I Station: N/A
Unit: N/A 1 Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
- , e
P
Inspector:JEFF SIEBEL-Comments:Obtain plumbing permit and inspections for new
water heater installed.
r _ — Location: back kitchen storage area
I I
i. C:'• A,!; 1 . gri4,% irs
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove ladder from back exit hall
Location: Not Provided
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such as oily rags,shall be stored in a
ignition. listed disposal container.Contents of such containers shall be removed and
disposed of daily.
Inspector:JEFF SIEBEL-Comments: Provide an approved, listed oily waste receptacle
for all oil saturated materials.See attached:
Location:Not Provided
Printed on 10/20/2023 @ 09:08
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space. Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments: Remove obstructions to electrical panel clearly
marked no storage from past violations.Maintain a minimum of 36"clearance at all
times.
Location:back kitchen storage area
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEFF SIEBEL-Comments:remove freezers in back room from power strip.
Each appliance must plug directly into wall outlet.
404
Location: Not Provided
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments: Remove extension cord under TV,behind POS by
hall to bathroom. Power strip with manual reset may be used for light duty electronic
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-09/28/2023 @ 08:44 annual inspection$80
Printed on 10/20/2023 @ 09:08
Page 2of3
REINSPECTION DATE
11/08/2023
CONTACT SIGNATURE
Freddy
Signed on:09/28/2023 @ 08:41 / L
L1
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:09/28/2023 @ 08:41
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 10/20/2023 @ 09:08
Page 3 of 3