HomeMy WebLinkAbout40 W SAN MARNAN O T INVOICE DATE DUE DATE INVOICE# TOTAL DUE
11/01/2023 12/10/2023 2024-00000148 $80.00
• .Yef tY" t •
.,..,,.. V 0
4I h.
44'
7d1'N
Customer#: 6854 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
FAREWAY 715 Mulberry St
40 W SAN MARNAN DR WATERLOO, IA 50703
WATERLOO,IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION -40 W SAN MARNAN - 10-11-23 FOR BILLING INQUIRY: (319)291-4323
LDescription ( Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
6854 11/01/2023 12/10/2023 2024-00000148 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
(45
L
WATERLOO FIRE RESCUE gortp
INSPECTION REPORT
FAREWAY,40 W SAN MARNAN DR,BLDG 40 W SAN MARNAN DR,WATERLOO/A S0701
DETAILS
Inspection Date: 10/1 1/2023 Inspection Type:Annual Inspection(1 Yr) Inspection Number:9176 Shift: N/A Station: N/A
Unit: N/A j Lead Inspector:JEFF SIEBEL ; Other Inspectors: N/A i Fee:$80.00
STATUS CODE DESCRIPTION
I L 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments: Repair egress light.
Location:Above Buns on South end of bread aisle
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:Provide annual fire sprinkler inspection with all
discrepancies corrected.Contractor must upload report online to the compliance
engine.
Location: Not Provided
F.-!L 906.7-Hangers and brackets. Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied.Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Properly mount fire extinguisher on bracket in
accessible location 4"to 5'above floor.Currently on floor.
Location: By fire sprinkler riser.
REINSPECTION DATE
10/30/2023
CONTACT SIGNATURE
Allen Weimerskich L d I�
Signed on: 10/13/2023 @ 12:45 C
y
Printed on 10/13/2023 @ 12:46
Page 1 of 2
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:10/13/2023 @ 12:45
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 10/13/2023 @ 12:46
Page 2of2