COMMERCIAL INSPECTION -250 WESTFIELD AVE- 10-12-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23522 11/01/2023 12/10/2023 2024-00000155 $610.00
Less Prepayment $0.00
Total Due S610.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
COURTYARD BY MARRIOT,250 WESTFIELD AVE,BLDG 250 WESTFIELD AVE,WATERLOO IA
5070'1 (a•f2)S7.
DETAILS
Inspection Date: 10/12/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:9779 ! Shift: N/A I Station: N/A i
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A ! Fee:$610.00
STATUS CODE DESCRIPTION
F ,Is_ 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments: Keep set-up in lobby clear of fire exit doors from
banquet hall.Future violations will result in requirement of signage on outside of
banquet doors.
Location: Banquet exit doors
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:Repair exit light
Location: By room 401
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair exit light
Location:Stair By room 441
Printed on 10/13/2023 @ 15:36
Page 1 of 7
STATUS CODE DESCRIPTION
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments: Provide documentation of testing and repair of all
emergency egress and exit lights with signature and date.Report may be mailed to
fire inspector.
Location: Not Provided
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:provide current annual standpipe inspection
report with all discrepancies corrected.current report from Ahearn dated 8/31/2023
lists discrepancies.Contractor must upload corrections online to the compliance
engine.
Location:Stand pipe
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments: Provide current annual fire sprinkler inspection
report with all discrepancies corrected. Report from Ahearn dated 8/2023 lists
discrepancies.Contractor must upload corrections online to the compliance engine.
Location:Not Provided
FAIL 5704.2.3.2-Label or placard. Tanks more than 100 gallons(379 L)in capacity,which are permanently installed or
mounted and used for the storage of Class I,II or III liquids,shall bear a label and
placard identifying the material therein.Placards shall be in accordance with NFPA
704.Exceptions:1.Tanks of 300-gallon(1136 L)capacity or less located on private
property and used for heating and cooking fuels in single-family dwellings.2.Tanks
located underground.
Inspector:JEFF SIEBEL-Comments:Relocate NFPA 704 Placard to location by door
frame to acid room to allow visual warning for fire fighters.
Location: Pool mechanical room
Printed on 10/13/2023 @ 15:36
Page 2 of 7
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:Remove extension cords from servers. Install
permanent power or listed power strip with a manual reset button may be used.
Location:Telecom Rooms all floors
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances.Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:remove extension cord.
Location: Room 520
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:Provide current documentation of dryer vent
cleaning to the outside of the building with signature and date.report may be
emailed to inspector.
Location:Customer and Commercial Clothes dryer
Printed on 10/13/2023 @ 15:36
Page 3 of 7
STATUS CODE DESCRIPTION
FpiiL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:repair sheetrock wall
Location:Storage room by maintenance
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1 Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Replace 3 missing ceiling tiles.
Location: Back hall by Starbecks
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:fire door must completely self-close and latch
Location:storage room by fitness room
Printed on 10/13/2023 @ 15:36
Page 4 of 7
STATUS CODE DESCRIPTION
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:fire door must completely self-close and latch
Location:Stair 3 to 2nd floor
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments: Fire door must completely self-close and latch
Location: Mechanical room by room 621
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:fire door must completely self-close and latch
Location: Pool equipment room door
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:fire door must completely self-close and latch
Location:Telecom room by room 425
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:fire door must completely self-close and latch
Location:Access Door behind dryers
FAIL 903.3.1 -Standards. Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1,unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other
chapters of this code,as applicable.
Inspector:JEFF SIEBEL-Comments:Fire Sprinkler head corroded.Fire sprinkler
contractor must replace fire sprinkler head.
Location: Room 622
Printed on 10/13/2023 @ 15:36
Page 5of7
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10.Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:Fire extinguishers due now.
Location: Not Provided
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:Provide current annual Fire Alarm inspection
report.Current report from Midwest dated 11/30/23 lists deficiencies.Contractor
must upload online to the compliance engine.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-10/13/2023 @ 15:20 Annual Inspection fee$610
JEFF SIEBEL-10/13/2023 @ 15:20 kitchen hood fire suppression inspection due 10/9/23
JEFF SIEBEL-10/13/2023 @ 15:21 private fire hydrant inspection due 11/4
REINSPECTION DATE
11/02/2023
Printed on 10/13/2023 @ 15:36
Page 6of7
CONTACT SIGNATURE
Corbin Simmons i
Signed on: 10/13/2023 @ 15:30 1(cGi
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:10/13/2023 @ 15:30