HomeMy WebLinkAbout1934 WASHINGTON ST O F W A l� INVOICE DATE DUE DATE INVOICE# TOTAL DUE
A .p
'1/40 07/20/2023 08/25/2023 2024-00000060 $80.00
u.,rir�rv► O
4S i v t7`�
Customer#: 4620 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
MAMA NICK'S CIRCLE PIZZERIA 715 Mulberry St
1934 WASHINGTON ST WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1934 Washington ST- 7-20-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4620 07/20/2023 08/25/2023 2024-00000060 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
0
1, k0
2
WATERLOO FIRE RESCUE �A�ERtoo
INSPECTION REPORT
MAMA NICK'S PIZZA,1934 WASHINGTON ST,BLDG 1934 WASHINGTON ST,WATERLOO IA
50702 4406\
DETAILS
Inspection Date:07/20/2023 Inspection Type:Annual Inspection(1Yr) ; Inspection Number:8956 Shift: N/A Station: N/A
Unit: N/A ; Lead Inspector:JEFF SIEBEL i Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Inspector:JEFF SIEBEL-Comments:Contractors must obtain plumbing and electrical
permits for new washer and dryer.
Location:new washer and dryer.
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit/egress
Location:Above North Exit Door
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:None
Location: Not Provided
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments:Fire door must completely self-close and latch
Location:Basement hall to basement dining room door
Printed on 07/21/2023 @ 13:38
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every
system service. six months and after activation of the system. Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the fire code official
upon completion.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood fire
suppression inspection report with all deficiencies corrected.Contractor must
upload online to the compliance engine.
Location: Not Provided
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:Provide current annual fire alarm inspection,
testing inspection with all discrepancies corrected.Contractor must upload online to
the compliance engine.Currently 217 days past due.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-07/21/2023 @ 13:16 kitchen hood cleaning due 9/7/23
JEFF SIEBEL-07/21/2023 @ 13:16 annual inspection$80
REINSPECTION DATE
08/09/2023
CONTACT SIGNATURE
George Nicholas CL /G n
Signed on:07/21/2023 @ 13:28 ✓ A
/11
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:07/21/2023 @ 13:29
Printed on 07/21/2023 @ 13:38
Page 2 of 3
.
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 07/21/2023 @ 13:38
Page 3 of 3