COMMERCIAL INSPECTION- 3545 W AIRLINE HWY- 7-19-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 1 $40.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13695 07/20/2023 08/25/2023 2024-00000062 $50.00
Less Prepayment $0.00
Total Due—+ $50.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
c
• WATERLOO FIRE
RESCUE
INSPECTION REPORT r
BMC AGGREGATES L.C.,3545 W AIRLINE HWY,BLDG 3545 W AIRLINE HWY,WATERLOO U 4240\
50703
DETAILS
Inspection Date:07/19/2023 Inspection Type:Annual Inspection(1Yr) j Inspection Number:205 I Shift: N/A Station: N/A
Unit: N/A ; Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$50.00
STATUS CODE DESCRIPTION
FAIL 2304.3.5-Emergency An approved emergency procedures sign,in addition to the signs required by Section
procedures. 2305.6,shall be posted in a conspicuous location and shall read:IN CASE OF FIRE,
SPILL OR RELEASE 1.USE EMERGENCY PUMP SHUTOFF 2.REPORT THE ACCIDENT!FIRE
DEPARTMENT TELEPHONE NO. FACILITY ADDRESS
Inspector:JEREMIAH VANDYKE-Comments:As described in the code,signage
needed.
Location:Shed with diesel tank behind weigh station building.
FAIL 2305.5-Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum
rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not
more than 75 feet(22 860 mm)from pumps,dispensers or storage tank fill-pipe
openings.
Inspector:JEREMIAH VANDYKE-Comments:Fire extinguisher must be outside
building in weather proof cabinet in conspicuous space.
Location:Shed with diesel tank behind weigh station building.
FAIL 2306.4-Physical protection. Guard posts complying with Section 312 or other approved means shall be provided
to protect above-ground tanks against impact by a motor vehicle unless the tank is
listed as a protected above-ground tank with vehicle impact protection.
Inspector:JEREMIAH VANDYKE-Comments: Please call fire inspector about this and
what can be used around building.319-883-1615.
Location:Shed with diesel tank behind weigh station building.
Printed on 07/20/2023 @ 16:42
Page 1 of 4
• STATUS CODE DESCRIPTION
FAIL 5703.5-Labeling and signage. The fire code official is authorized to require warning signs for the purpose of
identifying the hazards of storing or using flammable liquids.Signage for
identification and warning such as for the inherent hazard of flammable liquids or
smoking shall be provided in accordance with this chapter and Sections 5003.5 and
5003.6.
Inspector:JEREMIAH VANDYKE-Comments:Signage stating Diesel and combustibles
on east and west side of building.
Location:Shed with diesel tank behind weigh station building.
FAIL 5704.2.3.1 -Smoking and Signs shall be posted in storage areas prohibiting open flames and smoking.Signs
open flame. shall comply with Section 5703.5.
Inspector:JEREMIAH VANDYKE-Comments:No smoking signage needed on east and
west side of building.
Location:Shed with diesel tank behind weigh station building.
FAIL 5704.2.3.2-Label or placard. Tanks more than 100 gallons(379 L)in capacity,which are permanently installed or
mounted and used for the storage of Class I, II or III liquids,shall bear a label and
placard identifying the material therein. Placards shall be in accordance with NFPA
704.Exceptions: 1.Tanks of 300-gallon(1136 L)capacity or less located on private
property and used for heating and cooking fuels in single-family dwellings.2.Tanks
located underground.
Inspector:JEREMIAH VANDYKE-Comments:NFPA 704 Signage needed X2 on shed on
east and west side.
Location:Shed with diesel tank behind weigh station building.
FAIL 5704.2.7.3.3-Vent pipe Vent pipe outlets for tanks storing Class I,II or IIIA liquids shall be located such that
outlets the vapors are released at a safe point outside of buildings and not less than 12 feet
(3658 mm)above the finished ground level.Vapors shall be discharged upward or
horizontally away from adjacent walls to assist in vapor dispersion.Vent outlets shall
be located such that flammable vapors will not be trapped by eaves or other
obstructions and shall be not less than 5 feet(1524 mm)from building openings or
lot lines of properties that can be built on.Vent outlets on atmospheric tanks storing
Class IIIB liquids are allowed to discharge inside a building where the vent is a
normally closed vent. Exception:Vent pipe outlets on tanks storing Class IIIB liquid
inside buildings and connected to fuel-burning equipment shall be located such that
the vapors are released to a safe location outside of buildings.
Inspector:JEREMIAH VANDYKE-Comments:Vent pipe must be discharged to outside
per the code.Needs to be installed and maintained in accordance to tank
manufacture.
Location:Shed with diesel tank behind weigh station building.
GENERAL NOTES
Printed on 07/20/2023 @ 16:42
Page 2 of 4
JEREMIAH VANDYKE-07/20/2023 @ 16:39 Please contact Fire inspector if their are any questions. Lieutenant J.D.Van Dyke Fire
Investigator/Fire Inspector Waterloo Fire Rescue 319-291-4460-Office 319-883-1615-
Cell jeremiah.vandyke@waterloo-ia.org
JEREMIAH VANDYKE-07/19/2023 @ 16:10 Fire Extinguishers serviced by Pro Shield in 2023.
JEREMIAH VANDYKE-07/19/2023 @ 16:10 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-07/19/2023 @ 16:10 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-07/19/2023 @ 16:10 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-07/19/2023 @ 16:11 Inspection Fee=$50.00
REINSPECTION DATE
08/19/2023
CONTACT SIGNATURE
Mike Even-BMC Reason for not collecting a signature: NA