HomeMy WebLinkAbout2710 CROSSROADS BLVD F W 4 rks INVOICE DATE DUE DATE INVOICE# TOTAL DUE
08/10/2023 09/15/2023 2024-00000084 $200.00
rr sr!rr r• •rr i
•
o
Customer#: 5204 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
TIRES PLUS 715 Mulberry St
2710 CROSSROADS WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-2710 CROSSROADS BLVD - 8-3-23 FOR BILLING INQUIRY: (319)291-4323
L DescriptionI Total Price
REINSPECTION 3 $200.00
1712
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
5204 08/10/2023 09/15/2023 2024-00000084 $200.00
Less Prepayment $0.00
Total Due— $200.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT i
TIRES PLUS,2710 CROSSROADS BLVD,BLDG 2710 CROSSROADS BLVD,WATERLOO/A 50702
DETAILS
Inspection Date:08/03/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number: 10598 Shift: N/A ; Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A I Fee:$200.00
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm in trouble,needs to be
addressed by licensed fire alarm contractor.
U
2
Location: Not Provided
L.3
6
gx i s
> '=3
ki l
FAIL 509.1 -Identification Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements shall be identified for the use of the
fire department.Approved signs required to identify fire protection equipment and
s ,at equipment location shall be constructed of durable materials, permanently installed
and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Door located in main garage going into
tire storage area needs signage.Must have"Sprinkler Riser,FACP,&Main Electrical
panel"for description.
N
Location: Not Provided
Printed on 08/03i2023 @ 15:43
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments: Egress lights located in shop and in back
parts area tested and failed.
Location: Not Provided
41
•
•
•
•
•
• �R _
R
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm need to be inspected by
licensed fire alarm contractor and inspection report uploaded into Compliance
Engine by servicing contractor.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-06/30/2023 @ 13:00 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/30/2023 @ 13:00 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/30/2023 @ 13:00 RE-inspection fee:$200.00
Printed on 08/03/2023 @ 15:43
Page 2of3
REINSPECTION DATE
09/02/2023
CONTACT SIGNATURE
Scott Graham-District Manager Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE /� J
Signed on:08/03/2023 @ 15:42
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Primed on 08/03/2023 @ 15:43
Page 3 of 3