COMMERCIAL INSPECTION-2060 CROSSROADS BLVD - 8-3-23 FOR BILLING INQUIRY: (319)291-4323
Description ITotal Price]
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13921 08/10/2023 09/15/2023 2024-00000082 $80.00
Less Prepayment $0.00
Total Due--> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
„/),C12,•.\
•
WA TERL OO FIRE RESCUE �PTER��O
INSPECTION REPORT
CHINA EXPRESS,2060 CROSSROADS BLVD,BLDG 2060 CROSSROADS BLVD-STE 242,
WATERLOO/A 50702 4410
DETAILS
Inspection Date:08/03/2023 j Inspection Type:Annual Inspection(1Yr) Inspection Number: 10786 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL ! Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light
Location: By bathroom
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
• Inspector:JEFF SIEBEL-Comments:repair egress light
Location: kitchen above ice machine
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:Repair exit/egress light
Location:kitchen
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEFF SIEBEL-Comments:remove multi-plug adapter.
Location:kitchen
Printed on 08/04/2023 C 10:48
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:remove extension cord from ceiling.Any device
that produces heat,cooling or has a motor must plug directly into a wall outlet.
Location:Kitchen area
FAIL 807.2-Combustible In Groups A, B, E, I, M and R-1 and in dormitories in Group R-2,curtains,draperies,
decorative materials. fabric hangings and other similar combustible decorative materials suspended from
walls or ceilings shall comply with Section 807.3 and shall not exceed 10 percent of
the specific wall or ceiling area to which such materials are attached. Fixed or
movable walls and partitions,paneling,wall pads and crash pads applied structurally
or for decoration,acoustical correction,surface insulation or other purposes shall be
considered to be interior finish,shall comply with Section 803 and shall not be
considered decorative materials or furnishings. Exceptions: 1.In auditoriums in
Group A,the permissible amount of curtains,draperies,fabric hangings and similar
combustible decorative material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is equipped throughout with
an approved automatic sprinkler system in accordance with Section 903.3.1.1,and
where the material is installed in accordance with Section 803.15 of the International
Building Code.2.In Group R-2 dormitories,within sleeping units and dwelling units,
the permissible amount of curtains,draperies,fabric hangings and similar decorative
materials suspended from walls or ceilings shall not exceed 50 percent of the
aggregate wall areas where the building is equipped throughout with an approved
automatic sprinkler system installed in accordance with Section 903.3.1.3.In Group B
and M occupancies,the amount of combustible fabric partitions suspended from the
ceiling and not supported by the floor shall comply with Section 807.3 and shall not
be limited.4.The 10-percent limit shall not apply to curtains,draperies,fabric
hangings and similar combustible decorative materials used as window coverings.
Inspector:JEFF SIEBEL-Comments:Remove hanging curtains from dining room or
provide documentation of complying with NFPA Standards for flame and smoke
spread.
Location:dining room
GENERAL NOTES
JEFF SIEBEL-08/04/2023 @ 10:45 annual inspection$80
REINSPECTION DATE
08/23/2023
Printed on 08/04/2023 @ 10:48
Page 2 of 3
CONTACT SIGNATURE
Steven He
Signed on:08/04/2023 @ 10:46 L
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/04/2023 @ 10:46