HomeMy WebLinkAbout2122 KIMBALL AVE OF W q TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
( 08/10/2023 09/15/2023 2024-00000087 $80.00
u,,rirrra► O
• 1 1 •
T � O
3S l v')
Customer#: 15369 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
DAMON'S SPORTS BAR& GRILL 715 Mulberry St
2122 KIMBALL AV WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 2122 KIMBALL AVE- 8-1-23 FOR BILLING INQUIRY: (319)291-4323
l Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15369 08/10/2023 09/15/2023 2024-00000087 $80.00
Less Prepayment $0.00
Total Due— _ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
DAMON'S,2122 KIMBALL AVE,BLDG 2122 KIMBALL AVE,WATERLOO IA 50701 " ` '
DETAILS
Inspection Date:08/01/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:8684 Shift: N/A I Station: N/A I
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such as oily rags,shall be stored in a
ignition. listed disposal container.Contents of such containers shall be removed and
disposed of daily.
Inspector:JEFF SIEBEL-Comments:Provide an approved listed oily waste container
with self closing lid.
Location: Not Provided
FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: 1. Provide current semi-annual kitchen hood
exhaust system cleaning report with all discrepancies corrected.Contractor must
post report online to the compliance engine.2. Replace broken grease filter and
clean all filters.
Location:kitchen hood exhaust cleaning/inspection
GENERAL NOTES
JEFF SIEBEL-08/02/2023 @ 09:53 annual inspection$80
JEFF SIEBEL-08/02/2023 @ 09:54 Hood Ansul system due for service 8/25/23
REINSPECTION DATE
08/22/2023
Printed on 08/02/2023 @ 09:57
Page 1 of 2
CONTACT SIGNATURE
Michelle Koontz
Signed on:08/02/2023 @ 09:55
t/ C-_
r �
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/02/2023 @ 09:55
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 08/022023 @ 09:57
Page 2 of 2